background image

176169-BIM-A-0206

Unitary Products Group

5

DUCT WORK

These units are adaptable to downflow use as well as rear 
supply and return air duct openings. To convert to downflow, 
use the following steps:

1.

Remove the duct covers found in the bottom return and 
supply air duct openings. There are four (4) screws 
securing each duct cover (save these screws to use later).

2.

Install the duct covers, removed in step one, to the rear 
supply and return air duct openings. Secure with the four 
(4) screws used in step one.

3.

Seal the duct covers with silicone caulking.

Downflow units must have an L-shaped supply duct without any 
outlets or registers located directly below the supply outlet of 
the unit.

Duct work should be designed and sized according to the 
methods of the Air Conditioning Contractors of America 
(ACCA), as set forth in their Manual D.

A closed return duct system shall be used. This shall not 
preclude use of economizers or ventilation air intake. Flexible 
joints may be used in the supply and return duct work to 
minimize the transmission of noise.

NOTE: 

Be sure to note supply and return openings.

Refer to Figure 7 for information concerning rear and bottom 
supply and return air duct openings.

FILTERS

Single phase units are shipped without a filter and is the 
responsibility of the installer to secure a filter 

in the return air 

ductwork or install a Filter/Frame Kit

 (1FF0114).

A filter rack and a filters are standard on three phase units.

Filters must always be used and must be kept clean. When 
filters become dirt laden, insufficient air will be delivered by the 
blower, decreasing your units efficiency and increasing 
operating costs and wear-and-tear on the unit and controls.

Filters should be checked monthly especially since this unit may 
be used for both heating and cooling.

CONDENSATE DRAIN

A condensate trap is required to be installed in the condensate 
drain. The plumbing must conform to local codes. Use a sealing 
compound on male pipe threads. Install the condensate drain 
line (¾“ NPTF) to spill into an open drain.

SERVICE ACCESS

Access to all serviceable components is provided by the 
following removable panels:

• Blower service access

• Electrical/filter access

• Compressor service access

Refer to Figure 7 for location of these access panels and 
minimum clearance.

THERMOSTAT

The room thermostat should be located on an inside wall 
approximately 56" above the floor where it will not be subject to 
drafts, sun exposure or heat from electrical fixtures or 
appliances. Follow manufacturer's instructions enclosed with 
the thermostat for general installation procedure. Four, five or 
six color coded insulated wires (minimum #18 AWG) should be 
used to connect thermostat to unit. See Figure 2.

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of the current 
N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances. 
The unit must be electrically grounded in accordance with local 
codes or, in their absence, with the N.E.C./C.E.C. Voltage 
tolerances which must be maintained at the compressor 
terminals during starting and running conditions are indicated 
on the unit Rating Plate and Table 1.

The wiring entering the cabinet must be provided with 
mechanical strain relief.

A fused or HACR breaker disconnect switch should be field 
provided for the unit. If any of the wire supplied with the unit 
must be replaced, replacement wire must be of the type shown 
on the wiring diagram.

Electrical line must be sized properly to carry the load. Each 
unit must be wired with a separate branch circuit fed directly 
from the meter panel and properly fused.

Refer to Figure 2 for typical field wiring and to the appropriate 
unit wiring diagram for control circuit and power wiring 
information.

COMPRESSORS

Units are shipped with compressor mountings factory-adjusted 
for shipping.

COOLING

The following sequences of operation are based on using a 
standard single-stage cooling thermostat.

When fastening duct work to the side duct flanges on 
the unit, insert the screws through the duct flanges only. 
DO NOT insert the screws through the casing. Outdoor 
duct work must be insulated and waterproofed.

Loosen compressor mounting bolts half turn before 
operating unit.

Summary of Contents for DAPM024

Page 1: ...alert installer that personal injury and or equipment damage may result if installation procedure is not handled properly CAUTION READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT SAVE THIS...

Page 2: ...ATURE UTILIZES A THERMAL EXPANSION VALVE 12 6 DAPM060 SUCTION PRESSURE TEMPERATURE UTILIZES A THERMAL EXPANSION VALVE 12 7 DIMENSIONS AND CLEARANCES 13 8 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPP...

Page 3: ...information REFERENCE Additional information on the design installation operation and service of this equipment is available in the following reference forms 55 70 N1 General Installation 55 70 N2 Pre...

Page 4: ...of unit to 1 8 maximum RIGGING OR HANDLING Care must be exercised when moving the unit Do not remove any packaging until the unit is near the place of installation Rig unit with slings placed under t...

Page 5: ...ine NPTF to spill into an open drain SERVICE ACCESS Access to all serviceable components is provided by the following removable panels Blower service access Electrical filter access Compressor service...

Page 6: ...12 9 12 9 16 4 16 4 CHARGE REFRIGERANT 22 lbs oz 4 10 4 13 4 6 4 12 6 0 7 12 FILTER FACE AREA Sq Ft Qty Size 2 14 1 14 x 22 COMPRESSOR HERMETIC QTY 1 Type Recip Recip Scroll Scroll Scroll Scroll 1 ECM...

Page 7: ...96 40 036 208 230 1 60 187 253 15 4 88 1 2 4 3 24 8 30 30 0 96 40 042 208 230 1 60 187 253 21 1 115 1 2 6 8 34 4 45 45 0 96 40 048 208 230 1 60 187 253 20 5 115 1 2 6 8 33 6 45 45 0 96 40 060 208 230...

Page 8: ...06 2 11 3 15 0 54 2 62 5 76 4 86 6 80 90 80 90 2NH04502006 2 15 0 20 0 72 2 83 3 98 6 112 7 100 125 100 125 2NH04502506 2 18 8 25 0 90 3 104 2 121 5 138 7 125 150 125 150 060 208 230 1 60 25 0 169 0 1...

Page 9: ...d conditions would be inaccurate To ensure a dry coil the compressors should be deactivated while the test is being run 4 Knowing the pressure drop across a dry coil the actual CFM through the unit ca...

Page 10: ...1 1 22 9 24 6 26 3 27 7 29 2 30 6 32 1 70 15 0 16 7 18 4 20 1 21 8 23 5 25 3 26 7 28 1 29 6 31 0 75 13 9 15 7 17 4 19 1 20 8 22 5 24 2 25 6 27 1 28 5 30 0 80 12 9 14 6 16 3 18 0 19 7 21 4 23 2 24 6 26...

Page 11: ...100 5 0 5 9 6 8 9 3 11 8 14 2 16 7 105 7 0 9 3 11 7 14 0 110 6 9 9 1 11 3 115 6 5 8 6 TABLE 10 DAPM048 SUPERHEAT CHARGING TABLE OUTDOOR TEMPERATURE F SUPERHEAT AT COMPRESSOR SUCTION F AIRFLOW 400 CFM...

Page 12: ...MAL EXPANSION VALVE FIGURE 5 DAPM060 SUCTION PRESSURE TEMPERATURE UTILIZES A THERMAL EXPANSION VALVE FIGURE 6 DAPM060 SUCTION PRESSURE TEMPERATURE UTILIZES A THERMAL EXPANSION VALVE 287 225 5 8 7 03 5...

Page 13: ...H ZLWKRXW QRWLFH HUWLILHG GLPHQVLRQV ZLOO EH SURYLGHG XSRQ UHTXHVW 81 7 21 16 7 211 7 21 137 75 3 5 48 5 29 5 6 6833 5 23 1 1 6 5 7851 5 23 1 1 2035 6625 6 59 66 203 570 17 3 1 92 7 211 12 287 92 7 21...

Page 14: ...is in the AUTO position the 24 volt G signal will be removed and after a 30 second delay the indoor blower motor will shut down HEATING WITH POWER TO UNIT AND THERMOSTAT IN HEATING MODE 1 If the fan...

Page 15: ...R 1 1 SECOND DELAY ON FAN 10 SECOND DELAY OFF OFF HEATER BANK 3 HTR 4 HTR 5 INSTANT OFF HEATER BANK 2 HTR 2 HTR 3 SEC DELAY ON HEATER BANK 1 HTR 1 1 SECOND DELAY ON FAN 10 SECOND DELAY OFF TABLE 12 TH...

Page 16: ...d to clean the coil be sure that the power to the unit is shut off prior to cleaning TROUBLESHOOTING Prior to any of the following maintenance procedures shut off all power to the unit to avoid person...

Page 17: ...176169 BIM A 0206 Unitary Products Group 17 Notes for wiring diagrams on pages 18 thru 21 Legend for wiring diagrams on pages 18 thru 21 6 F 9 N O T U S E D 2 M 3 2 3 0 V C O IL...

Page 18: ...176169 BIM A 0206 18 Unitary Products Group FIGURE 8 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY DPM MODELS 15556BBSH0301 SEE DETAIL A...

Page 19: ...176169 BIM A 0206 Unitary Products Group 19 FIGURE 9 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY DPM MODELS...

Page 20: ...176169 BIM A 0206 20 Unitary Products Group FIGURE 10 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY DPM MODELS...

Page 21: ...176169 BIM A 0206 Unitary Products Group 21 FIGURE 11 TYPICAL WIRING DIAGRAM 460 3 60 POWER SUPPLY DPM MODELS...

Page 22: ...176169 BIM A 0206 22 Unitary Products Group...

Page 23: ...176169 BIM A 0206 Unitary Products Group 23...

Page 24: ...t to change without notice Printed in U S A 176169 BIM A 0206 Copyright 2006 by Unitary Products Group All rights reserved Supersedes 161697 BIM A 1005 Unitary 5005 Norman Products York OK Group Drive...

Reviews: