![Unitary products group DAPM024 Installation Manual Download Page 15](http://html1.mh-extra.com/html/unitary-products-group/dapm024/dapm024_installation-manual_4004904015.webp)
176169-BIM-A-0206
Unitary Products Group
15
TABLE 11: THERMOSTAT SIGNALS (SINGLE PHASE UNITS)
SIGNAL STATE
BOARD FUNCTION
SIGNAL STATE
BOARD FUNCTION
“G”
ON
FAN INSTANT ON
OFF
FAN INSTANT OFF
“G”
“y”
ON
FAN INSTANT ON
COMPRESSOR AND OUTDOOR FAN INSTANT ON
“W1”
ON
FAN INSTANT ON
HEATER BANK 1 (HTR 1) INSTANT ON
OFF
COMPRESSOR AND OUTDOOR FAN INSTANT OFF
FAN 60 SECOND DELAY OFF ON DEH MODELS
FAN 30 SECOND DELAY OFF ON DEM MODELS
OFF
HEATER BANK 1 (HTR 1) INSTANT OFF
FAN 10 SECOND DELAY OFF
“G”
“W1"
ON
FAN INSTANT ON
HEATER BANK 1 (HTR 1) INSTANT ON
“W2"
ON
FAN INSTANT ON
HEATER BANK 1 (HTR 1) INSTANT ON
HEATER BANK 2 (HTR 2 & HTR 3) 10 SEC. DELAY ON
OFF
HEATER BANK 1 (HTR 1) INSTANT OFF
FAN 10 SECOND DELAY OFF
OFF
HEATER BANK 2 (HTR 2 & HTR 3) INSTANT OFF
HEATER BANK 1 (HTR 1) ½ SEC. DELAY OFF
FAN 10 SECOND DELAY OFF
“G”
“W1"
”W2”
ON
FAN INSTANT ON
HEATER BANK 1 (HTR 1) INSTANT ON
HEATER BANK 2 (HTR 2 & HTR 3) 10 SEC. DELAY ON
HEATER BANK 3 (HTR 4 & HTR 5) 20 SEC. DELAY ON
“G”
“W1"
”W2”
ON
FAN INSTANT ON
HEATER BANK 1 (HTR 1) INSTANT ON
HEATER BANK 2 (HTR 2 & HTR 3) 10 SEC. DELAY ON
HEATER BANK 3 (HTR 4 & HTR 5) 20 SEC. DELAY ON
OFF
HEATER BANK 3 (HTR 4 & HTR 5) INSTANT OFF
HEATER BANK 2 (HTR 2 & HTR 3) ½ SEC. DELAY ON
HEATER BANK 1 (HTR 1) 1 SECOND DELAY ON
FAN 10 SECOND DELAY OFF
OFF
HEATER BANK 3 (HTR 4 & HTR 5) INSTANT OFF
HEATER BANK 2 (HTR 2 & HTR 3) ½ SEC. DELAY ON
HEATER BANK 1 (HTR 1) 1 SECOND DELAY ON
FAN 10 SECOND DELAY OFF
TABLE 12: THERMOSTAT SIGNALS (THREE PHASE UNITS)
SIGNAL STATE
BOARD FUNCTION
SIGNAL STATE
BOARD FUNCTION
“G”
ON
FAN INSTANT ON
OFF
FAN INSTANT OFF
“G”
“y”
ON
FAN INSTANT ON
COMPRESSOR AND OUTDOOR FAN INSTANT ON
“W1”
ON
FAN INSTANT ON
HEATER BANK 1 (HTR 1, 2 & 3) INSTANT ON
OFF
COMPRESSOR AND OUTDOOR FAN INSTANT OFF
FAN 60 SECOND DELAY OFF ON DEH MODELS
FAN 30 SECOND DELAY OFF ON DEM MODELS
OFF
HEATER BANK 1 (HTR 1, 2 & 3) INSTANT OFF
FAN 10 SECOND DELAY OFF
“G”
“W1"
ON
FAN INSTANT ON
HEATER BANK 1 (HTR 1, 2 & 3) INSTANT ON
“W2"
ON
FAN INSTANT ON
HEATER BANK 1 (HTR 1, 2 & 3) INSTANT ON
HEATER BANK 2 (HTR 4, 5 & 6) 10 SEC. DELAY ON
OFF
HEATER BANK 1 (HTR 1, 2 & 3) INSTANT OFF
FAN 10 SECOND DELAY OFF
OFF
HEATER BANK 2 (HTR 4, 5 & 6) INSTANT OFF
HEATER BANK 1 (HTR 1, 2 & 3) ½ SEC. DELAY OFF
FAN 10 SECOND DELAY OFF
“G”
“W1"
”W2”
ON
FAN INSTANT ON
HEATER BANK 1 (HTR 1, 2 & 3) INSTANT ON
HEATER BANK 2 (HTR 4, 5 & 6) 10 SEC. DELAY ON
“W1"
”W2”
ON
FAN INSTANT ON
HEATER BANK 1 (HTR 1, 2 & 3) INSTANT ON
HEATER BANK 2 (HTR 4, 5 & 6) 10 SEC. DELAY ON
OFF
HEATER BANK 2 (HTR 4, 5 & 6) ½ SEC. DELAY OFF
HEATER BANK 1 (HTR 1, 2 & 3) 1 SECOND DELAY OFF
FAN 10 SECOND DELAY OFF
OFF
HEATER BANK 2 (HTR 4, 5 & 6) ½ SEC. DELAY ON
HEATER BANK 1 (HTR 1, 2 & 3) 1 SECOND DELAY ON
FAN 10 SECOND DELAY OFF