TABLE 4: ELECTRICAL DATA (BASIC UNIT)
MODEL
DPM
POWER
SUPPLY
VOLTAGE
LIMITATIONS
1
1. Rated in accordance with ARI Standard 110, utilization range “A”.
COMPRESSOR COND.
FAN
MOTOR,
FLA
SUPPLY
AIR BLOWER
MOTOR, FLA
MIN.
CIRCUIT
AMPACITY
(AMPS)
2
2. Dual element, time delay type.
MAX.
FUSE
SIZE
(AMPS)
MAX.
HACR
BREAKER
SIZE
(AMPS)
UNIT
POWER
FACTORY
TRANSFORMER
SIZE
(VA)
MIN.
MAX.
RLA
LRA
024
208/230-1-60 187
253
10
55
1.2
4.3
18
25
25
0.96
40
030
208/230-1-60 187
253
11.2
68
1.2
4.3
19.5
25
25
0.96
40
036 208/230-1-60 187
253
15.4
88
1.2
4.3
24.8
30
30
0.96
40
042
208/230-1-60 187
253
21.1
115
1.2
6.8
34.4
45
45
0.96
40
048 208/230-1-60 187
253
20.5
115
1.2
6.8
33.6
45
45
0.96
40
060 208/230-1-60 187
253
25
169
1.2
9.1
41.6
50
50
0.96
40
036
208/230-3-60 187
253
10.2
77
1.2
4.3
18.3
25
25
0.96
75
042
208/230-3-60 187
253
13.4
89
1.2
6.8
24.8
30
30
0.96
75
048 208/230-3-60 187
253
14.1
90
1.2
6.8
25.6
35
35
0.96
75
060 208/230-3-60 187
253
17.3
123
1.2
9.1
31.9
40
40
0.96
75
036
460-3-60 432
504
5.1
39
0.75
4.3
9.3
15
15
0.96
75
042
460-3-60 432
504
6.4
45
0.75
6.8
12.2
15
15
0.96
75
048 460-3-60 432
504
7.1
45
0.75
6.8
12.9
15
15
0.96
75
060 460-3-60 432
504
7.4
49.5
0.75
9.1
14.6
20
20
0.96
75