background image

176169-BIM-A-0206

4

Unitary Products Group

INSTALLATION

LIMITATIONS

These units must be installed in accordance with the following 
national and local safety codes.

1.

National Electrical Code ANSI/NFPS No. 70 or Canadian 
Electrical Code Part 1, C22.1 (latest editions).

2.

Local plumbing and waste water codes and other 
applicable local codes.

Refer to Table 1 for unit application data and to Tables 5 and 6 
for electric heat application data.

If components are to be added to a unit to meet local codes, 
they are to be installed at the dealer's and/or the customer's 
expense.

Size of unit for proposed installation should be based on heat 
loss/heat gain calculations made in accordance with industry 
recognized procedures identified by the Air Conditioning 
Contractors of America.

LOCATION

Use the following guidelines to select a suitable location for 
these units.

1.

Unit is designed for outdoor installation only.

2.

Condenser must have an unlimited supply of air. Where a 
choice of location is possible, position unit on either north 
or east side of building.

3.

For ground level installation, a level pad or slab should be 
used. The thickness and size of the pad or slab used 
should meet local codes and unit weight. Do not tie the 
slab to the building foundation.

4.

For roof top installation, be sure the structure will support 
the weight of the unit plus any field installed components. 
Unit must be installed on a level roof curb or appropriate 

angle iron frame providing adequate support under the 
compressor/condenser section.

5.

Maintain level tolerance of unit to 1/8" maximum.

RIGGING OR HANDLING

Care must be exercised when moving the unit. Do not remove 
any packaging until the unit is near the place of installation. Rig 
unit with slings placed under the unit. Spreader bars of 
sufficient length should be used across the top of the unit.

BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT 
IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT 
WILL LIFT EVENLY.

Units may also be moved or lifted with a fork-lift. Slotted 
openings in the skid are provided for this purpose. Forks must 
pass completely through the base.

FIGURE 1: CENTER OF GRAVITY

Refer to Table 2 for unit weights and to Figure 1 for approximate 
center of gravity.

CLEARANCES

All units require certain clearances for proper operation and 
service. Refer to Figure 7 for the clearances required for 
combustion, construction, servicing and proper unit operation.

:

TABLE 1: UNIT APPLICATION DATA

Voltage Variation

Min. / Max.

1

1. Rated in accordance with ARI Standard 110, utilization 

range “A”.

208/230V

2

2.  “T1" transformer primary tap must be moved from the 

230 volt connection to the 208 volt connection for low 
voltage applications of 208 volt and below.

187 / 253

460V

432 / 504

575V

540 / 630

Wet Bulb Temperature (°F) of Air on 

Evaporator Coil,        Min. / Max.

57 / 72

Dry Bulb Temperature (°F) of Air on

Condenser Coil,        Min.

3

 / Max.

3. A low ambient accessory is available for operation 

down to 0°F

45 / 120

TABLE 2: UNIT WEIGHTS

UNIT

SIZE

SHIPPING 

WEIGHT 

(lbs.)

OPERATING 

WEIGHT 

(lbs.)

CORNER WEIGHTS

(location, lbs.)

“A”

“B”

“C”

“D”

024

338

333

91

80

78

88

030

340

335

86

83

83

87

036

341

336

92

81

79

89

042

348

343

94

83

80

91

048

376

371

94

89

94

99

060

456

451

127

122

101

106

Do not permit overhanging structures or shrubs to 
obstruct the condenser air discharge outlet.

&(17(52)*5$9,7<

)5217

2)

81,7

³$´

³%´

³&´

³'´

Summary of Contents for DAPM024

Page 1: ...alert installer that personal injury and or equipment damage may result if installation procedure is not handled properly CAUTION READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT SAVE THIS...

Page 2: ...ATURE UTILIZES A THERMAL EXPANSION VALVE 12 6 DAPM060 SUCTION PRESSURE TEMPERATURE UTILIZES A THERMAL EXPANSION VALVE 12 7 DIMENSIONS AND CLEARANCES 13 8 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPP...

Page 3: ...information REFERENCE Additional information on the design installation operation and service of this equipment is available in the following reference forms 55 70 N1 General Installation 55 70 N2 Pre...

Page 4: ...of unit to 1 8 maximum RIGGING OR HANDLING Care must be exercised when moving the unit Do not remove any packaging until the unit is near the place of installation Rig unit with slings placed under t...

Page 5: ...ine NPTF to spill into an open drain SERVICE ACCESS Access to all serviceable components is provided by the following removable panels Blower service access Electrical filter access Compressor service...

Page 6: ...12 9 12 9 16 4 16 4 CHARGE REFRIGERANT 22 lbs oz 4 10 4 13 4 6 4 12 6 0 7 12 FILTER FACE AREA Sq Ft Qty Size 2 14 1 14 x 22 COMPRESSOR HERMETIC QTY 1 Type Recip Recip Scroll Scroll Scroll Scroll 1 ECM...

Page 7: ...96 40 036 208 230 1 60 187 253 15 4 88 1 2 4 3 24 8 30 30 0 96 40 042 208 230 1 60 187 253 21 1 115 1 2 6 8 34 4 45 45 0 96 40 048 208 230 1 60 187 253 20 5 115 1 2 6 8 33 6 45 45 0 96 40 060 208 230...

Page 8: ...06 2 11 3 15 0 54 2 62 5 76 4 86 6 80 90 80 90 2NH04502006 2 15 0 20 0 72 2 83 3 98 6 112 7 100 125 100 125 2NH04502506 2 18 8 25 0 90 3 104 2 121 5 138 7 125 150 125 150 060 208 230 1 60 25 0 169 0 1...

Page 9: ...d conditions would be inaccurate To ensure a dry coil the compressors should be deactivated while the test is being run 4 Knowing the pressure drop across a dry coil the actual CFM through the unit ca...

Page 10: ...1 1 22 9 24 6 26 3 27 7 29 2 30 6 32 1 70 15 0 16 7 18 4 20 1 21 8 23 5 25 3 26 7 28 1 29 6 31 0 75 13 9 15 7 17 4 19 1 20 8 22 5 24 2 25 6 27 1 28 5 30 0 80 12 9 14 6 16 3 18 0 19 7 21 4 23 2 24 6 26...

Page 11: ...100 5 0 5 9 6 8 9 3 11 8 14 2 16 7 105 7 0 9 3 11 7 14 0 110 6 9 9 1 11 3 115 6 5 8 6 TABLE 10 DAPM048 SUPERHEAT CHARGING TABLE OUTDOOR TEMPERATURE F SUPERHEAT AT COMPRESSOR SUCTION F AIRFLOW 400 CFM...

Page 12: ...MAL EXPANSION VALVE FIGURE 5 DAPM060 SUCTION PRESSURE TEMPERATURE UTILIZES A THERMAL EXPANSION VALVE FIGURE 6 DAPM060 SUCTION PRESSURE TEMPERATURE UTILIZES A THERMAL EXPANSION VALVE 287 225 5 8 7 03 5...

Page 13: ...H ZLWKRXW QRWLFH HUWLILHG GLPHQVLRQV ZLOO EH SURYLGHG XSRQ UHTXHVW 81 7 21 16 7 211 7 21 137 75 3 5 48 5 29 5 6 6833 5 23 1 1 6 5 7851 5 23 1 1 2035 6625 6 59 66 203 570 17 3 1 92 7 211 12 287 92 7 21...

Page 14: ...is in the AUTO position the 24 volt G signal will be removed and after a 30 second delay the indoor blower motor will shut down HEATING WITH POWER TO UNIT AND THERMOSTAT IN HEATING MODE 1 If the fan...

Page 15: ...R 1 1 SECOND DELAY ON FAN 10 SECOND DELAY OFF OFF HEATER BANK 3 HTR 4 HTR 5 INSTANT OFF HEATER BANK 2 HTR 2 HTR 3 SEC DELAY ON HEATER BANK 1 HTR 1 1 SECOND DELAY ON FAN 10 SECOND DELAY OFF TABLE 12 TH...

Page 16: ...d to clean the coil be sure that the power to the unit is shut off prior to cleaning TROUBLESHOOTING Prior to any of the following maintenance procedures shut off all power to the unit to avoid person...

Page 17: ...176169 BIM A 0206 Unitary Products Group 17 Notes for wiring diagrams on pages 18 thru 21 Legend for wiring diagrams on pages 18 thru 21 6 F 9 N O T U S E D 2 M 3 2 3 0 V C O IL...

Page 18: ...176169 BIM A 0206 18 Unitary Products Group FIGURE 8 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY DPM MODELS 15556BBSH0301 SEE DETAIL A...

Page 19: ...176169 BIM A 0206 Unitary Products Group 19 FIGURE 9 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY DPM MODELS...

Page 20: ...176169 BIM A 0206 20 Unitary Products Group FIGURE 10 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY DPM MODELS...

Page 21: ...176169 BIM A 0206 Unitary Products Group 21 FIGURE 11 TYPICAL WIRING DIAGRAM 460 3 60 POWER SUPPLY DPM MODELS...

Page 22: ...176169 BIM A 0206 22 Unitary Products Group...

Page 23: ...176169 BIM A 0206 Unitary Products Group 23...

Page 24: ...t to change without notice Printed in U S A 176169 BIM A 0206 Copyright 2006 by Unitary Products Group All rights reserved Supersedes 161697 BIM A 1005 Unitary 5005 Norman Products York OK Group Drive...

Reviews: