SAGEON PSMC I PRODUCT MANUAL
PM990-2999-00, Rev 5
3-4
1. Plant Voltage
2. Ambient Temp.
3. Temp. String 1
4. Temp. String 2
5. Load Voltage
6. Feed Current 1
.
.
.
14. Feed Current 9
15. Plant Current
16. PCB Temperature
The last value read before entering the
Status
menu is displayed for each channel.
The user can update the displayed channel by pressing the “
Select
” key. Press
“
Escape
” once to return to the main
Select Mode
menu.
Alarms:
The
Alarm
menu provides quick access to detailed alarm identification. The menu
is accessed with the “
Next
” or “
Previous
” keys and entered with the “
Select
” key.
The initial screen displays the current number of active alarms and the status of the
audible alarm cut-off (ACO control will not be displayed if the audible alarm has
been disabled in Configure/System options). Here, the “
Select
” key toggles the
audible alarm on or off when it is enabled.
The “
Next
” and “
Previous
” keys take the user through each active alarm, showing
the source of the alarm; i.e., Alarm 1 of 3: RFA 3; or Alarm 1 of 1: LOW
VOLTAGE.
The LED alarm indicators on the front panel provide general information that
corresponds to the detailed alarm information. The LED’s may indicate a fuse
alarm and a rectifier fail alarm currently exist. The
Alarm
menu tells the user
which specific fuse type and rectifier is in alarm. Pressing “
Escape
” when
completed, will return the user to the main
Select Mode
Menu.
Configure:
The
Configure
menu provides all of the sub-menus necessary to custom
configure the SAGEON PSMC I for a particular application. Pressing “
Select
”
when the
Configure
menu appears allows access to the configuration menus.
“
Next
” and “
Previous
” keys are used to locate the desired sub-menu. Pressing
“
Select
” again accesses the displayed menu. The
Configure
menu consists of
eight standard and one optional sub-menu (
Equalize
):
Manual Equalize:
Optional menu that appears when
Timer
mode is selected under
Systems Options EQUALIZE MENU
. In Timer mode the user can set the
desired Equalize time from 1 to 255 hours in the Configure Manual EQ Time
menu. The
Equaliz
e menu appears first when enabled so the user can quickly
access the time parameter for the manual equalize mode. Pressing “
Next
” or
“
Previous
” moves the user to the next/last
Configure
sub-menu, “
Escape”
moves
the user back to the main
Configure
menu.
Enable Thresholds:
Lets the user decide which alarm thresholds are active and which are
not. The user presses “
Select
” to enter the menu, then “
Next
” or “
Previous
” to
access each alarm threshold. The “
Select
” key can be used to toggle each alarm
threshold on or off. See Setting up the Analog Channels section of this manual for
more details. Pressing the “
Escape
” key when complete returns the user to the