SAGEON PSMC I PRODUCT MANUAL
PM990-2999-00, Rev 5
4-2
to access other test modes. Press “
Escape
” to return to the main menus or the idle display screen.
4.4 TEST OUTPUT RELAYS
Press “
Select
” when the
Output Relays
menu appears to enter the output relay test mode. The first
output relay will appear with its current status “
Open
” or “
Closed
” displayed and updated
continuously. The output relays are accessed in the following order using the “
Next/Up
” key:
1. Major
7. Temp
13. AUX
2. All
8. Minor
14. EQ
3. VLVA
9. HVA
15. RS
4. LVD
10. LVA
16. HVSD
5. RFA
11. CTRL INH
6. FA
12. CEMF
Pressing the “
Select
” key when a specific output relay is displayed will toggle that relay
Open
(off)
or
Closed
(on). In the special case of “ALL” relays, all output relays will either be closed or open
concurrently. The user can press “
Next
” or “
Previous
” keys to move through the list of output relays
channels. The output relay status will automatically return to its controlled state when the user
leaves the output relay test mode.
Note:
The front panel alarm LED’s will not indicate relay status in the output relay test mode.
CAUTION:
Alarms that are connected to a remote alarm monitor will send false ‘nuisance’ alarm
status if toggled while in the output relay test mode.
Warning:
Turning the control relays for Equalize or HVSD on in the test mode will result in the
power plant entering that mode. The power plant rectifiers will be shutdown if the
HVSD output relay is turned on; the rectifiers will also be shut down if the test “ALL”
relays option is used. If the power plant has been commissioned use extreme caution
when testing these relays to make sure that power plant operation will not be adversely
affected.
The output relay test mode can be very useful during the power plant test and acceptance to verify
operation. Rectifier response to Equalize, HVSD, and Restart can be checked. External audible or
visual monitors can be tested. Alarm call outs can be verified, etc.
When completed, press “
Escape
” to return to the
Select Test
display. Press “
Next
” or “
Previous
”
to access other test modes. Press “
Escape
” to return to the main menus or the idle display screen.
4.5 LED TEST MODE
Press “
Select
” when the display reads
LAMP OFF
to activate all front panel LED’s at once. All
LED’s should be illuminated. Press “
Select
” to perform the test again, or press “
Escape
” at anytime
to exit the test.
Note:
The LED’s test will automatically end after approx. 10 seconds. Press “
Select
” again, if
desired, to start the test again.