Alarms & Warning:
When the red triangle on the top left lights, one or more alarms are activated.
When the red key on the left lights, the output N05-C5 is active and the relay
KTRS
switches the resistors OFF.
Check the reason, correct the failure and, as soon as the temperature is lower than
trS
, reset it through
ALA
/
rES .
In order to show active alarms and warnings, select the relevant menu through
ALA
/
Act
.and, using the
UP
and
DOWN
buttons, scroll the lines.
In order to perform the manual reset, select
ALA
/
rES
.
Code
Description
Sourse
Active simbol
Reset type
trS
High temperature resistors alarm
probe Pb4 > value trS red key
Manual
EP1
Probe Pb1 fault
Probe Pb1 fault
red triangle
Automatic
EP2
Probe Pb2 fault
Probe Pb2 fault
red triangle
Automatic
EP3
Probe Pb3 fault
Probe Pb3 fault
red triangle
Automatic
EP4
Probe Pb4 fault
Probe Pb4 fault
red triangle
Automatic
Set point adjustment:
All the parameters inside the
Par
menu are locked by a password. The user can modify only set points, without
using any passwords.
The oil viscosity at the nozzle, should be about 1,5°E, which guarantees correct and safe functioning of the burner.
The temperature values in the table, guarantee the respect of that parameter and are valid when the pre heating
tank is installed on the burner. For different configurations , please refer to the chapter "Recommendations to
design heavy oil feeding plants" on the burner manual
Here below recommended set points:
Menu path
Oil viscosity at 50 °C according to the letter shown in the
burner model
P N E D H
89 cSt
< 50 cSt
> 50 cSt
< 110 cSt
> 110 cSt
< 400 cSt
> 400 cSt
< 4000 cSt
12 °E
< 7°E
> 7 °E
< 15 °E
> 15 °E
< 50 °E
> 50 °E
< 530 °E
Par
rEG Pb1 tr
Oil heater temperature
probe
parameter not visible
Pb2 tCI
Plant consent
temperature probe
(when installed)
20 °C
70 °C
70 °C
70 °C
---
Pb3 Oil
oil heater output
temperature probe (PID
regulation);
60-70 °C
110-120 °C 120-130 °C 130-140 °C 140-150 °C
SP0 Set-point oil heater with
oil pump stopped
(stand-by)
45 °C
120 °C
130 °C
140 °C
150 °C
Pb4 tcn Oil heater consent
temperature probe
40 °C
100 °C
100 °C
110 °C
120 °C
trS
Safety temperature tank
resistors
(manual reset)
120 °C
190-200 °C 190-200 °C 190-200 °C 190-200 °C
The above temperature values are suggested and refer to a plant designed according to the prescriptions in the
burner user manual.
The suggested values can change in reference to the fuel oil specifications.
Summary of Contents for PBY1025
Page 40: ...C I B UNIGAS M039126CE 40...
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ......
Page 81: ...RWF55 5X RWF55 6X User manual M12926CA Rel 0 2 11 2023...
Page 82: ...2 DEVICE INSTALLATION Fixing system Drilling dimensions...
Page 103: ......
Page 104: ...23 Note Specifications and data subject to change Errors and omissions excepted...
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......