PART III: OPERATION
36
1
.the first parameter will be “954”: the percentage of flame is shown on the right. By pr or - it is possible to scroll up/down the
parameter list.
2
Once the last parameter is accessed (143) by pressing
+
, the
End
message will blink.
3
PressPress
InFo
for more than three seconds or for more than three seconds orto return to the normal display.
For further nformation, see tha LMV2 related manual.
ADJUSTMENTS FOR GAS OPERATION
Air flow and gas adjustment
startup the burner by selecting GAS by means of the switch on the burner control panel
Adjust the air and gas flow rates, in according to the “air/gas ratio” curvepoints setting procedure on the LMV manual,. Check con-
tinuosly, the flue gas analisys, to avoid combustion with air excess.
Once the butterfly valve is completely opened, acting on the pressure stabiliser of the valves group, adjust the
gas flow rate in the
high flame stage
as to meet the values requested by the boiler/utilisation:
If necessary, change the combusiton head positionl.
The air and gas flow rate are now adjusted at the maximum power stage: go on with the point to point adjustement, as to reach the
minimum output
Adjust the pressure switches
Adjusting the gas valves group
Multibloc MB-DLE
The multibloc unit is a compact unit consisting of two valves, gas pressure switch, pres-
sure stabilizer and gas filter.
The valve is adjusted by means of the
RP
regulator after slackening the locking screw
VB
by a number of turns. By unscrewing the regulator
RP
the valve opens, screwing the valve
closes. To set the fast opening remove cover
T
, reverse it upside down and use it as a tool
to rotate screw
VR
. Clockwise rotation reduces start flow rate, anticlockwise rotation incre-
ases it.
Do not use a screwdriver on the screw
VR
!
The pressure stabilizer is adjusted by operating the screw
VS
located under the cover
C
.
By screwing down the pressure is increased and by unscrewing it is reduced.
Note: the screw
VSB
must be removed only in case of replacemente of the coil.
C
VS
T(VR)
RP
VB
VSB
Summary of Contents for K590X
Page 49: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Page 56: ...8 Parameters level heating engineer...
Page 98: ...50 ERROR CODE TABLE...
Page 99: ...51...
Page 100: ...52...
Page 101: ...53...
Page 102: ...54...
Page 103: ...55...
Page 104: ...56...
Page 105: ...57...
Page 106: ...58...
Page 107: ...59...
Page 108: ...60...
Page 109: ...61...
Page 110: ...62...
Page 111: ...63...
Page 112: ...64...
Page 117: ......
Page 118: ......
Page 119: ......