PART II: INSTALLATION
24
BURNERS WITH INVERTER VARIANT (if provided)
The
LMV51.300 / LMV52.xxx e LMV37.400/LMV26.300
electronic cam burners with fan motor driven by inverter in addition to the air
and fuel adjustment curves also have a fan motor speed adjustment curve.
The
LMV5x
equipment through a sensor controls the fan motor revolutions and with a signal in
4÷20mA
controls it through the inverter.
The
LMV2x
equipment through a sensor controls the fan motor revolutions and with a signal in
0÷10V
controls it through the inverter.
Generally the curve of the inverter goes from 50% to 100% of the engine revolutions. This, in addition to improving the setting of the
burner also allows a saving on the consumption of the fan engine..
Terminal interface with Inverter
DANFOSS
Type
Model
LMV5
XXXXX
M-. MD. xx. xx. x. x. xxx. EI.
XXXXX
M-. MD. xx. xx. x. x. xxx. EG.
XXXXX
MG. MD. xx. xx. x. x. xxx. EK.
XXXXX
MG. MD. xx. xx. x. x. xxx. ER.
LMV2x/3x
XXXXX
M-. MD. xx. xx. x. x. xxx. EB.
XXXXX
MG. MD. xx. xx. x. x. xxx. EC.
Danfoss FC101
Danfoss FC102
Two series of interchangeable Inverters version with
Inverter FC101 and FC102
LMV5
LMV2x/3x
Braking resistances
possibility of use only for
FC102
Summary of Contents for K590X
Page 49: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Page 56: ...8 Parameters level heating engineer...
Page 98: ...50 ERROR CODE TABLE...
Page 99: ...51...
Page 100: ...52...
Page 101: ...53...
Page 102: ...54...
Page 103: ...55...
Page 104: ...56...
Page 105: ...57...
Page 106: ...58...
Page 107: ...59...
Page 108: ...60...
Page 109: ...61...
Page 110: ...62...
Page 111: ...63...
Page 112: ...64...
Page 117: ......
Page 118: ......
Page 119: ......