PART I: SPECIFICATIONS
14
POWER REDUCTION WITH REFERENCE TO THE BURNER OPERATING CURVE
Since depowering the burner operating range is equivalent to increasing the burner power by the same percentage, the quickest proce-
dure is described point by point below:
Choosing the burner without taking flue gas recirculation into account
estimate the amount of recirculation (see figure below) required to ensure a certain NOx value as a function of the heat load of the
boiler, for that burner
multiply the required burned power by the depowering factor expressed as follows
multiply the back pressure in the combustion chamber by the depressurisation factor squared (pressure losses vary with the
square of the change in flow rate)
choose the burner considering the new power and back pressure value
if the burner size is insufficient, a larger machine must be selected, the depowering factor must be re-checked and the above pro-
cedure repeated.
Gas pressure
in
comb
usti
on hea
d
K590X M-..
Stm
3
/h
K750X M-..
Stm
3
/h
Ga
s pre
ssu
re
in
co
mb
ust
ion
h
ea
d
K660X M-..
Stm
3
/h
Gas pressure
in
comb
usti
on hea
d
K590X L-..
Stm
3
/h
K750X L-..
Stm
3
/h
Summary of Contents for K590X
Page 49: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Page 56: ...8 Parameters level heating engineer...
Page 98: ...50 ERROR CODE TABLE...
Page 99: ...51...
Page 100: ...52...
Page 101: ...53...
Page 102: ...54...
Page 103: ...55...
Page 104: ...56...
Page 105: ...57...
Page 106: ...58...
Page 107: ...59...
Page 108: ...60...
Page 109: ...61...
Page 110: ...62...
Page 111: ...63...
Page 112: ...64...
Page 117: ......
Page 118: ......
Page 119: ......