PART IV: MAINTENANCE
38
Gas filter maintenance
Removing the combustion head
MultiBloc MBE
MultiBloc VD Mounting
WARNING: Before opening the filter, close the manual cutoff valve downstream the filter and bleed the gas; check
that inside the filter there is no pressurised gas.
C
B
A
To clean or remove the filter, proceed as follows:
1 remove the cap unscrewing the fixing screws (A);
2 remove the filtering cartridge (B), clean it using water and soap, blow it
with compressed air(or replace it, if necessary)
3 replace the cartridge in its proper position taking care to place it
inbetween the guides as not to hamper the cap replacement;
4 be sure to replace the “O” ring into its place (C) and replace the cover
fastening by the proper screws (A).
Remove the lid C.
Unscrew the screws V holding in position the manifold G and pull out
the complete group as shown in figure.
Note: for the subsequent assembly carry out the above described
operations in the reverse order, checking the correct position of the OR ring.
To remove the combustion head, pull it out. Once removed, check that the air
and gas holes are not obstructed. Clean the combustion head by means of
compressed air or scrape off the scale using a metallic brush
VRT
OR
V
AR
G
C
position
to push
1
2
3
4
5
6
7
1. Position VD on VB, fig. 2+3.
2. Slide VD forward up to the stop, fig. 4.
3. Screw VD on with 2 M5 screws for each, max. 5 Nm/44 in.-lb., fig. 5/6.
4. VD can be mounted rotated by 180°, fig. 7.
Summary of Contents for E115X-FGR M Series
Page 42: ......
Page 43: ......
Page 45: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 52: ...8...
Page 56: ...12 2 2 LMV5x program structure...
Page 83: ...39...
Page 90: ......
Page 91: ......
Page 92: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 94: ...Annex1 Example for motor cable...
Page 95: ......
Page 96: ...Annex 2 Example for sensor cable...
Page 97: ......
Page 98: ......
Page 102: ......