PART I: SPECIFICATIONS
7
Technical Specifications
(*) NOTE ON THE BURNER WORKING SERVICE:
LMV2x automatically stops after 24h of continuous working. The device immedia-
telystarts up, automatically. LMV3x performs countinuous operation.
Country and usefulness gas categories
Fuel
BURNER TYPE
E115X-FGR M-..
E140X-FGR M-..
E190X-FGR M-..
Output
min. - max. kW
300 - 920
290 - 1120
290 - 1520
Fuel
Natural gas
Category
(see next paragraph)
Gas flow rate
min.-max. Stm
3
/h
32 - 97
31 - 119
31 - 161
Gas pressure
min.-max. mbar
(see Note 2)
Power supply
230V 3~ / 400V 3N ~ 50Hz
Total power consumption
kW
2,7
2,7
3,5
Fan motor power consumption
kW
2,2
2,2
3,0
Protection
IP40
Operation
MD - Fully modulating
Valves size / Gas connection - 40
1"
1/2
/
Rp1
1/2
1"
1/2
/
Rp1
1/2
1"
1/2
/
Rp1
1/2
Valves size / Gas connection - 50
2"
/
Rp2
2"
/
Rp2
2"
/
Rp2
Valves size / Gas connection - 65
2"
1/2
/
DN65
2"
1/2
/
DN65
2"
1/2
/
DN65
Valves size / Gas connection - 80
3"
/
DN80
3"
/
DN80
3"
/
DN80
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service (*)
Continuous
Note1:
All gas flow rates are referred to Stm
3
/ h (1.013 mbar absolute pressure, 15° C temperature) and are valid for G20 gas
(net calorific value H
i
= 34,02 MJ / Stm
3
= 9,45 kWh / Stm
3
);
Note2:
Maximum gas pressure= 360 mbar (with
Dungs MBDLE)
Maximum gas pressure= 500 mbar (with
Siemens VGD or Dungs MultiBloc MBE)
Minimum gas pressure= see gas curves.
Warning:
Burners are suitable only for indoor operation with a maximum relative humidity of 80%
GAS
CAT
COUNTRY
I
2H
AT
ES
GR
SE
FI
IE
HU
IS
NO
CZ
DK
GB
IT
PT
CY
EE
LV
SI
MT
SK
BG
LT
RO
TR
CH
I
2E
LU
PL
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2E( R
BE
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
(*)
NL
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2ELL
DE
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2Er
FR
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
(*) Only for I
2EK
: the appliance was configured for the appliance category K (I2K) and is suitable for the use of G and G+ distribution gases according to the specifications as
included in the NTA 8837:2012 Annex D with a Wobbe index of 43.46 – 45.3 MJ/m3 (dry, 0 °C, upper value) or 41.23 – 42.98 (dry, 15 °C, upper value). This appliance can
moreover be converted and/or be calibrated for the appliance category E (I2E). This therefore implies that the appliance “is suitable for G+ gas and H gas or is demonstrably
suitable for G+ gas and can demonstrably be made suitable for H gas” within the meaning of the “Dutch Decree of 10 May 2016 regarding amendment of the Dutch Gas
Appliances Decree and the Dutch Commodities (Administrative Fines) Act in connection with the changing composition of gas in the Netherlands as well as technical
amendment of some other decrees.
DANGER! The burner must be used only with the fuel specified in the burner data
plate.
Type --
Model
--
Year --
S.Number --
Output --
Oil Flow
--
Fuel
--
Category --
Gas Pressure
--
Viscosity --
El.Supply --
El.Consump. --
Summary of Contents for E115X-FGR M Series
Page 42: ......
Page 43: ......
Page 45: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 52: ...8...
Page 56: ...12 2 2 LMV5x program structure...
Page 83: ...39...
Page 90: ......
Page 91: ......
Page 92: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 94: ...Annex1 Example for motor cable...
Page 95: ......
Page 96: ...Annex 2 Example for sensor cable...
Page 97: ......
Page 98: ......
Page 102: ......