PART III: OPERATION
34
Adjusting the combustion head
Head adjusting
The combustion head position affects the flame stability.The diffuser position must be set during the commissioning according to the
regulation needs. The diffuser position is factory set as shown in figure ”A” (x = 10 mm). If different settings are required, it is possible
to change the position: loosen the VB screw and slightly move the combustion head backwards, turning clockwise the knob VRT.
Fasten VB screw when the adjustment is accomplished.
Depending on the boiler application, it is possible to act on the holes (figure B) to improve the flame stability and NOx, CO emission
values. If necessary, close/open the holes in figure “B” using the screws kit given with the burner.
CAUTION:
perform these adjustments once the burner is turned off and cooled.
Attention! if it is necessary to change the head position, repeat the air and fuel adjustments described above.
“all-ahead” position
“all-backwards” head position
VRT
X
x = 10 mm
A
B
A
B
Summary of Contents for E115X-FGR M Series
Page 42: ......
Page 43: ......
Page 45: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 52: ...8...
Page 56: ...12 2 2 LMV5x program structure...
Page 83: ...39...
Page 90: ......
Page 91: ......
Page 92: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 94: ...Annex1 Example for motor cable...
Page 95: ......
Page 96: ...Annex 2 Example for sensor cable...
Page 97: ......
Page 98: ......
Page 102: ......