PART I: SPECIFICATIONS
6
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Fuel
The burner technical specifications, described in this manual, refer to natural gas (calorific net value Hi = 9.45 kWh/Stm
3
, density
ρ
=
0.717 Kg/Stm
3
) and LPG (calorific net value Hi = 26.79 kWh/Stm
3
, density
ρ
= 2.151 Kg/Stm
3
). For different fuel such as town gas and
biogas, multiply the values of flow and pressure by th corrective factors shown in the table below.
For example, to obtain the flow and pressure values for the biogas:
Type
E115X-FGR
Model
A.
1.
40.
EF
(1)
M-.
MD.
S
P
.
*.
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
1 BURNER TYPE
E115X-FGR, E140X-FGR, E190X-FGR
2 FUEL
M - Natural gas
3 OPERATION (Available versions)
MD - Fully modulating, PR - Progressive
4 BLAST TUBE
S - Standard L - Extended
5 DESTINATION COUNTRY
* - see data plate
6 BURNER VERSION
A - Standard, Y - Special
7 EQUIPMENT
0 = 2 gas valves
1 = 2 gas gas proving system
7 = 2 gas maximum gas pressure switch
8 = 2 gas gas proving maximum gas pressure switch
8 GAS CONNECTION see Specifications 40 = Rp1
1/2
50 = Rp2
65 = DN65
80 = DN80
100 = DN100
9 MICRO-PROCESSOR CONTROL
EF = Medium-large burners complete with electronic cam LMV5x and temperature-
compensated flue gas recirculation FGR, without O
2
monitoring, without inverter.
EG = Medium-large burners complete with electronic cam, inverter and temperature-
compensated flue gas recirculation, without O
2
monitoring
Fuel
Hi
(KWh/Stm
3
)
ρ
(kg/Stm
3
)
f
Q
f
p
Town gas
4,88
0,6023
1,936
3,3
Biogas
6,395
1,1472
1,478
3,5
LPG
26,79
2,151
0,353
0,4
ATTENTION! The combustion head type and the settings depend on the fuel. The burner must be used only for its
intended purpose specified in the burner data plate .
ATTENTION: the corrective factors in the above table depend on the gas composition, so on the calorifc value and
the density of the gas. The above value can be taken only as reference.
Q
biogas
Q
naturalGas
1 478
=
p
biogas
p
naturalGas
3 5
=
Summary of Contents for E115X-FGR M Series
Page 42: ......
Page 43: ......
Page 45: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 52: ...8...
Page 56: ...12 2 2 LMV5x program structure...
Page 83: ...39...
Page 90: ......
Page 91: ......
Page 92: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 94: ...Annex1 Example for motor cable...
Page 95: ......
Page 96: ...Annex 2 Example for sensor cable...
Page 97: ......
Page 98: ......
Page 102: ......