NRT/NRM COMMISSIONING
Once the NRT/NRM has been installed and all connections made, field commissioning
can be conducted. If any of the commissioning tests fail, more information may be found
in the appendix. Commissioning tests are as follows:
8.1
NRT/NRM Powered On
Confirm that the status LED, visible through the infra red window on the front of the unit, is
flashing. With the NRT/NRM in an idle state the LED will flash faintly once every second.
8.2
NRT/NRM Initialised
•
Confirm proper functioning by connecting the NRT/NRM to a laptop computer.
•
Launch the STARLOG 4 ( laptop computer ) application.
•
Launch the Test window.
•
Check the file and firmware version number.
•
If the NRT/NRM returns a value then the NRT/NRM has firmware installed as well
as all required files.
•
NRT/NRM Field Signal Verification.
•
Connect a laptop computer to the NRT/NRM.
•
Launch the STARLOG 4 application.
•
From the STARLOG 4 menu select the scheme corresponding to the NRT/NRM.
•
Select the test Mode
•
The Com window will be displayed showing communications with the NRT/NRM.
•
Press ALT+M to enter the NRT/NRM menu.
•
Press P and then E.
•
Enter 1234 then press Enter, then press ESC.
•
Press C, then S for signal it must be 16 or higher, if it is 99.99 then there is no
connection to the cellular network.
•
If there is sufficient signal, press ESC and ESC to exit.
8.3
NRT/NRM Initialisation
•
Reconnect to the NRT/NRM if not already connected.
•
Launch STARLOG 4 (laptop computer) application.
•
Select the test Mode.
•
Select toe diagnostics in the COMMS window and press CONNECT.