background image

 

 

 

 Touch Screen 

32 

 

Given the environmental temperature and the humidity, the Touch Screen remote control calculates the dew point. 

In operation of the plant in summer mode, with the double set-point  function active on chillers and thermoregulation normally 

made with the radiant panels (second set of work), it activates a control to keep the dew point of at least a quantity defined by the 

keyboard maintainer parameter 

Par42/65: 

"Dew-point temp. margin

 " °C below the ambient temperature detected by the control 

itself. 

Instead, when 

ambient temperature

 < 

Dew Point + Margin temp. Point

 

The fan coils for dehumidification turn on. 

 

The chiller start working with the set-point for the fan coils. 

The permanence remains in this status until the temperature returns to: 

Ambient temperature 

≥ 

Dew point + Dew temp.  1°C. 

Even in the case where the above condition is verified, it remains in the status  of dehumidification for at least the time set by 

maintainer parameter 

Par43/65: 

"Min. staying time in dehumidification

"

, in order to avoid annoying oscillations. 

If the above condition is not satisfied after a maximum time given by the maintainer parameter 

Par44/65

: "

Max Dehumidification 

time

", the machine comes out from dehumidification. To avoid returning immediately, in this case it requires a minimum staying in 

adjustment to the radiant panels, still given by 

Par43/65: 

"Max. staying time in dehumidification". 

 

4.11

 

CLIMATIC COMPENSATION 

It is possible to compensate the set-point according to outdoor temperature, in a different way between heating and cooling modes, 

first and second set-point. 

In such a case be sure that the 

b08

 parameter 

(System main page -> Configuration -> Service menu -> Parameters -> Chiller -> Chiller 

name -> 

b08:

 

Enab. dynamic set point)

 is disabled (=0) on the chiller. 

Setpoint

T ext

Set

Set Text

Offset

Offset

m2

m1

Setpoint

T ext

Set

Set Text

Offset

Offset

m2

m1

 

Figure 34. Climatic compensation. 

 

Set = T water, T water ECO o T

2

 water, T

2

 water ECO, settable from the page: ”

Set-point setup

” -> 

“Chiller”.

 

 

Offset

  = offset settable  from  the  page: ”

Set-point setup

”  -> 

“Chiller” 

(the variable  “

Offset

” appears only if the

  “m” 

coefficients have been configured

). 

 

Set Text

m1

m2

 = parameters which can be set from: “

Configuration”

 -> “

Service menu

” -> “

Parameters

” -> “

Keyboard

” 

(see paragraph Touch Screen control panel configuration parameters). 

To exclude the climatic compensation from the user, you have to set to zero all the offsets in the menu ”

Set-point setup

” -> 

“Chiller”.

 

To exclude the climatic compensation from the service, you have to set to zero the “

m

” coefficients in the service menu, keyboard 

parameters. 

The outdoor temperature is detected by a dedicated sensor already wired to the heat pump. 

 

Summary of Contents for TOUCH SCREEN N

Page 1: ...USER S AND INSTALLER S MANUAL LCD Touch Screen Centralized Remote Controller TOUCH SCREEN_N...

Page 2: ...4 SPECIAL FUNCTIONS PAGE 17 3 6 5 CONFIGURATION PAGE 17 3 6 6 HELP PAGE 19 4 MACHINES STATUS AND FUNCTIONS 20 4 1 NEWTORK MANAGEMENT 20 4 2 REMOTE CONTROL CONNECTION WITH MULTIPLE CHILLERS IN THE NETW...

Page 3: ...4 12 SECONDARY CIRCULATOR 33 4 13 OTHER FUNCTIONS 33 4 14 SPECIAL FUNCTIONS 33 4 14 1 SCREED FUNCTION 33 4 15 PASSWORD AND PROTECTIONS 34 5 REMOTE ACCESS 34 5 1 SECURITY 34 5 2 LOCAL WEB SERVER 34 6...

Page 4: ...ts and parameters of the first circuit can be displayed 1 2 USE NOT PERMITTED Any use different than that permitted is PROHIBITED 1 3 TECHNICAL DATA Features Nominal Min Max Power supply voltage 12Vac...

Page 5: ...the screens Do not put the touch screen in contact with other electrical devices Electrostatic discharge may cause a malfunction 2 1 3 DISPLAY The display is a TFT LCD 16 9 format with a diagonal 4 3...

Page 6: ...1 GNDR Ground touch screen RS 485 Modbus RTU GNDR Comunicazione Modbus X 5 1 R Modbus RTU touch screen signal R X 5 2 R Modbus RTU touch screen signal R 2 4 INSTALLATION The Touch Screen control is u...

Page 7: ...e The colour saturation indicates that icon is usable when pressed the related function is performed The transparency de saturated indicates that icon is not usable and any touch on it has no resultin...

Page 8: ...ss to information on the firmware version 6 Configuring the Ethernet network 7 Log out intermittent symbol if it s active 8 Arrow of navigation next page Graphically it also contains information on th...

Page 9: ...ctly the following information referreing to fancoil units Presence of fancoil unis that are connected to the network if the fancoil symbol appears on the display Figure 8 Fancoil units connected to t...

Page 10: ...5 Chiller heat pump with working signalling function given by the rotation of the fans from here you access to an additional page of information about that specific chiller 6 Active alarms of the disp...

Page 11: ...r temperature C Outlet water temperature C Sanitary probe temperature if it s present and configured C Accessing the same page with service or manufacturer access right to enable the access right pres...

Page 12: ...TARY INTEGRATION RESISTANCE 3 PLANT INTEGRATION RESISTANCE 4 BOILER ENABLEMENT 5 DOUBLE SET POINT 6 DEHUMIDIFYING 7 SLAB FEATURE 8 DEFROST 9 ANTIFREEZE WATER 10 ANTIFREEZE TRAY RESISTANCE Table 1 Orde...

Page 13: ...the next fancoil unit on the network 3 the name of the zone to which the fancoil belongs and the fancoil identification number are reported every time you press the name area you switch to the next fa...

Page 14: ...onfigured function but note active Herein below is reported a table with icons that may appear in the scrollable sidebar The presence absence of the icon in the sidebar depends on the status of its co...

Page 15: ...the system The field 3 indicates the chiller which it refers by pressing on it you progress to the next chiller in the network For each chiller shown you see the readings on the temperature of the wa...

Page 16: ...STATUS SETUP 2 SET POINT SETUP 3 PROGRAMS AND CHRONO THERMOSTAT In the bottom from the left to right 4 SPECIAL FUNCTIONS 5 CONFIGURATION 6 HELP MENU 3 6 1 STATUS SETUP PAGE Press the button to enter...

Page 17: ...age From this page you can set separately the weekly program of each chiller and zones of fancoils You can also program the legionella s cycle and the production of hot water if enabled see Paragraph...

Page 18: ...e pages of the parameters until you find the desired parameter press on the currently set value the present value turns red to indicate that it can be changed by using the up and down arrows Select th...

Page 19: ...ess the confirmation tick Note If you press outside the confirmation area it returns again the previously value 3 6 5 3 MANUFACTURER MENU To access to the manufacturer menu you must set the manufactur...

Page 20: ...connect the chiller and the remote control Touch Screen as shown in the drawing In the remote control Touch Screen by setting the parameter Par 8 65 Configuration Service Menu Keyboard related to the...

Page 21: ...the installation and utilization of the remote control panel for water terminal units management it is recommended to separately power on the water terminal units fancoils each terminal unit must be i...

Page 22: ...n is not totally configurable by Touch Screen controller It is necessary to act directly on the chiller heat pump on board controller only if present expansion module by setting the parameters H85 to...

Page 23: ...or the settings related to the function please refer to paragraph AMBIENT THERMOSTAT Note Once the status is set from the Touch Screen control panel you must wait a minute to ensure that communication...

Page 24: ...SET POINT Management procedure of the set point of the different zones and chillers 1 from the system main page go to Set point setup 2 at this point you find a list of assigned chillers and the areas...

Page 25: ...e zones in winter mode In addition if is enabled the sanitary mode from System main page Configuration Service menu Parameters Chiller Chiller name H10 sanitary presence 1 you can access to two other...

Page 26: ...rve that correspondingly to the selected time period you will see a time line bar of the colour of the type of the selected set if normal blue green when in economy mode no bar in Off repeat the above...

Page 27: ...is respectively Summer sanitary Winter sanitary Only sanitary 4 7 4 3 ZONES AND FANCOILS WEEKLY PROGRAM In a similar way to the scheduling of the chillers it is possible to set the weekly program of e...

Page 28: ...NT THERMOSTAT The Touch Screen control panel can operate as a typical ambient thermostat The ambient thermostat function for each zone will be enabled disabled using the corresponding button at the bo...

Page 29: ...SETTINGS PROCEDURE 4 8 1 SETTING OF LANGUAGE AND DATE TIME To set the keyboard language 1 from the system main page go to Configuration 2 then go to User menu 3 enter the user password and press the...

Page 30: ...ion of humidistat is instead carried out directly by the Touch Screen remote control panel by means of its integrated sensors and the logic internally implemented related to the control of dew point a...

Page 31: ...for the calculation of the dew point is the Magnus Tetens approximation this approximation is valid for values of Td between 0 C and 50 C therefore if the calculation gives a value out of these limit...

Page 32: ...o avoid returning immediately in this case it requires a minimum staying in adjustment to the radiant panels still given by Par43 65 Max staying time in dehumidification 4 11 CLIMATIC COMPENSATION It...

Page 33: ...oiler integration defrosting cycle water side or air side anti freeze heaters etc please refer to chillers and fancoils instructions manuals 4 14 SPECIAL FUNCTIONS From the main menu choosing the icon...

Page 34: ...unlock the screensaver set by default to 0 and modifiable by accessing to user s parameters see Paragraph 3 6 5 1 5 REMOTE ACCESS The device can interact with the local network by an Ethernet port acc...

Page 35: ...o shift to next available pages click on the links at the page bottom Figure 38 Touch Screen Ethernet Command page The commands present in the Command page are referred to the entire system The operat...

Page 36: ...t points set for the winter season water set point economy water set point and if enabled double set point second water set point and second water economy set point appear under Winter while under the...

Page 37: ...oard USB port For the upgrade copy the upgrade file in the main root of a USB pen drive insert the pen drive into the Touch Screen USB port enter into Configurations User s menu see Paragraph 3 6 5 1...

Page 38: ...C Heat 20 0 35 0 15 0 C 19 m5 comp Text FC 10 0 10 0 0 0 20 m6 comp Text FC 10 0 10 0 0 0 21 Set2 Text comp CHIL Cool 0 0 50 0 20 0 C 22 Set2 Text comp CHIL Heat 20 0 35 0 10 0 C 23 Second m1 comp Tex...

Page 39: ...um temp of the fancoils of the zone 2 Maximum temp of the fancoils of the zone 3 Temperature measured by the Touch Screen control panel 0 3 1 50 Regulation temperature in zone 5 Winter 0 Average temp...

Page 40: ...imum temp of the fancoils of the zone 2 Maximum temp of the fancoils of the zone 3 Temperature measured by the Touch Screen control panel 0 3 1 58 Regulation temperature in zone 4 Summer 0 Average tem...

Page 41: ...2 Maximum temp of the fancoils of the zone 3 Temperature measured by the Touch Screen control panel 0 3 1 63 Regulation temperature in zone 9 Summer 0 Average temp of the fancoils of the zone 1 Minim...

Page 42: ......

Page 43: ......

Page 44: ...printing errors It also reserves the right to modify its products as deemed necessary or useful without jeopardising their essential features 46033 casteldario mantova italia tel 39 0376 57001 fax 39...

Reviews: