background image

Touch Screen 

 

27 

The chronothermostat (configuration page) colourful time-lines shows: the blue time-line indicating normal operation, the green 

time-line indicating the economical operation, the red time-line  indicating the time in which the legionella  cycle is programmed 

(thus the machine in that condition may be active even if the scheduler is set to Off). 
 

4.7.4.2

 

WEEKLY PROGRAM SANITARY WATER PRODUCTION 

In a similar way to what is reported for the settings on the chronothermostat of chillers and fan coils, you can define when to enable 

the production of sanitary hot water (by setting the individual days of the week, with a minimum step of 15 minutes). The settings 

that you can do are: 

 

Normal: Enable function; 

 

Off: Disabled function. 

To set the programming, go to "

Programs

" -> "

Sanitary

” (the word "

Sanitary

" appears only if you have enabled the sanitary mode: 

System Main -> 

Configuration

 -> 

Service menu

 

-> Parameters

 -> 

Chiller

 -> 

Chiller name

 -> 

H10: Sanitary presence = 1

). 

The procedure for configuring the programmable chronothermostat is therefore similar to those described above, with the only 

difference that the choice of the operation is only between "

Normal

" and "

Off

" (see figure below). 

 

Figure 26. Chronothermostat, “Sanitary” page. 

In the period when the function is active, the machines enabled to produce sanitary water are placed in the seasonal operation of 

the plant scheduled by the plant scheduler with the addition of the sanitary mode, that is, respectively: 

 

 sanitary 

 

 sanitary  

 

Only sanitary  

 

4.7.4.3

 

ZONES AND FANCOILS WEEKLY PROGRAM 

In a similar way to the scheduling of the chillers, it is possible to set the “weekly program” of each individual zone independently of 

the summer and winter seasons, with a resolution of 15 minutes. 

The possible settings are: 

 

Zone in off mode; 

 

Zone in normal operation (normal room set-point temperature); 

 

Zone in economic operation (economic room set-point temperature 

Therefore entering the "Summer Zone" or "Winter Zone" the list of all the configured zones is displayed. At this point it is necessary 

to select the zone that you wish to set; the chronothermostat configuration procedure is then the same as that already reported for 

the chillers. In fact, the graphical appearance and functionalities of the page are identical to those already described. 

 

4.7.4.4

 

LEGIONELLA DISINFECTION WEEKLY PROGRAM FUNCTION 

If the sanitary function is enabled (from system main page -> 

Configuration

 -> 

Service menu

 -> 

Parameters

 

-> Chiller

 ->

 Chiller name 

-

H10:  Sanitary presence  = 1

), you can program the hours of the individual days of the week for activating the cycle of anti-

legionella disinfection.  

You select only the starting time (with 15 minutes steps), since the duration of the cycle is defined by a parameter with maintainer 

access rights (System main page --> 

Configuration

 -> 

Service menu

 -> 

Parameters

 -> 

Keyboard 

-> 

Par 31/65: Legionella disinfection 

enable time

)

.

 

To carry out the programming you must enter into “

Programs

” -> “Legionella disinfection”; the procedure is simple because you 

have to select only the starting day and hour for the cycle (see the below figure). 

 

Summary of Contents for TOUCH SCREEN N

Page 1: ...USER S AND INSTALLER S MANUAL LCD Touch Screen Centralized Remote Controller TOUCH SCREEN_N...

Page 2: ...4 SPECIAL FUNCTIONS PAGE 17 3 6 5 CONFIGURATION PAGE 17 3 6 6 HELP PAGE 19 4 MACHINES STATUS AND FUNCTIONS 20 4 1 NEWTORK MANAGEMENT 20 4 2 REMOTE CONTROL CONNECTION WITH MULTIPLE CHILLERS IN THE NETW...

Page 3: ...4 12 SECONDARY CIRCULATOR 33 4 13 OTHER FUNCTIONS 33 4 14 SPECIAL FUNCTIONS 33 4 14 1 SCREED FUNCTION 33 4 15 PASSWORD AND PROTECTIONS 34 5 REMOTE ACCESS 34 5 1 SECURITY 34 5 2 LOCAL WEB SERVER 34 6...

Page 4: ...ts and parameters of the first circuit can be displayed 1 2 USE NOT PERMITTED Any use different than that permitted is PROHIBITED 1 3 TECHNICAL DATA Features Nominal Min Max Power supply voltage 12Vac...

Page 5: ...the screens Do not put the touch screen in contact with other electrical devices Electrostatic discharge may cause a malfunction 2 1 3 DISPLAY The display is a TFT LCD 16 9 format with a diagonal 4 3...

Page 6: ...1 GNDR Ground touch screen RS 485 Modbus RTU GNDR Comunicazione Modbus X 5 1 R Modbus RTU touch screen signal R X 5 2 R Modbus RTU touch screen signal R 2 4 INSTALLATION The Touch Screen control is u...

Page 7: ...e The colour saturation indicates that icon is usable when pressed the related function is performed The transparency de saturated indicates that icon is not usable and any touch on it has no resultin...

Page 8: ...ss to information on the firmware version 6 Configuring the Ethernet network 7 Log out intermittent symbol if it s active 8 Arrow of navigation next page Graphically it also contains information on th...

Page 9: ...ctly the following information referreing to fancoil units Presence of fancoil unis that are connected to the network if the fancoil symbol appears on the display Figure 8 Fancoil units connected to t...

Page 10: ...5 Chiller heat pump with working signalling function given by the rotation of the fans from here you access to an additional page of information about that specific chiller 6 Active alarms of the disp...

Page 11: ...r temperature C Outlet water temperature C Sanitary probe temperature if it s present and configured C Accessing the same page with service or manufacturer access right to enable the access right pres...

Page 12: ...TARY INTEGRATION RESISTANCE 3 PLANT INTEGRATION RESISTANCE 4 BOILER ENABLEMENT 5 DOUBLE SET POINT 6 DEHUMIDIFYING 7 SLAB FEATURE 8 DEFROST 9 ANTIFREEZE WATER 10 ANTIFREEZE TRAY RESISTANCE Table 1 Orde...

Page 13: ...the next fancoil unit on the network 3 the name of the zone to which the fancoil belongs and the fancoil identification number are reported every time you press the name area you switch to the next fa...

Page 14: ...onfigured function but note active Herein below is reported a table with icons that may appear in the scrollable sidebar The presence absence of the icon in the sidebar depends on the status of its co...

Page 15: ...the system The field 3 indicates the chiller which it refers by pressing on it you progress to the next chiller in the network For each chiller shown you see the readings on the temperature of the wa...

Page 16: ...STATUS SETUP 2 SET POINT SETUP 3 PROGRAMS AND CHRONO THERMOSTAT In the bottom from the left to right 4 SPECIAL FUNCTIONS 5 CONFIGURATION 6 HELP MENU 3 6 1 STATUS SETUP PAGE Press the button to enter...

Page 17: ...age From this page you can set separately the weekly program of each chiller and zones of fancoils You can also program the legionella s cycle and the production of hot water if enabled see Paragraph...

Page 18: ...e pages of the parameters until you find the desired parameter press on the currently set value the present value turns red to indicate that it can be changed by using the up and down arrows Select th...

Page 19: ...ess the confirmation tick Note If you press outside the confirmation area it returns again the previously value 3 6 5 3 MANUFACTURER MENU To access to the manufacturer menu you must set the manufactur...

Page 20: ...connect the chiller and the remote control Touch Screen as shown in the drawing In the remote control Touch Screen by setting the parameter Par 8 65 Configuration Service Menu Keyboard related to the...

Page 21: ...the installation and utilization of the remote control panel for water terminal units management it is recommended to separately power on the water terminal units fancoils each terminal unit must be i...

Page 22: ...n is not totally configurable by Touch Screen controller It is necessary to act directly on the chiller heat pump on board controller only if present expansion module by setting the parameters H85 to...

Page 23: ...or the settings related to the function please refer to paragraph AMBIENT THERMOSTAT Note Once the status is set from the Touch Screen control panel you must wait a minute to ensure that communication...

Page 24: ...SET POINT Management procedure of the set point of the different zones and chillers 1 from the system main page go to Set point setup 2 at this point you find a list of assigned chillers and the areas...

Page 25: ...e zones in winter mode In addition if is enabled the sanitary mode from System main page Configuration Service menu Parameters Chiller Chiller name H10 sanitary presence 1 you can access to two other...

Page 26: ...rve that correspondingly to the selected time period you will see a time line bar of the colour of the type of the selected set if normal blue green when in economy mode no bar in Off repeat the above...

Page 27: ...is respectively Summer sanitary Winter sanitary Only sanitary 4 7 4 3 ZONES AND FANCOILS WEEKLY PROGRAM In a similar way to the scheduling of the chillers it is possible to set the weekly program of e...

Page 28: ...NT THERMOSTAT The Touch Screen control panel can operate as a typical ambient thermostat The ambient thermostat function for each zone will be enabled disabled using the corresponding button at the bo...

Page 29: ...SETTINGS PROCEDURE 4 8 1 SETTING OF LANGUAGE AND DATE TIME To set the keyboard language 1 from the system main page go to Configuration 2 then go to User menu 3 enter the user password and press the...

Page 30: ...ion of humidistat is instead carried out directly by the Touch Screen remote control panel by means of its integrated sensors and the logic internally implemented related to the control of dew point a...

Page 31: ...for the calculation of the dew point is the Magnus Tetens approximation this approximation is valid for values of Td between 0 C and 50 C therefore if the calculation gives a value out of these limit...

Page 32: ...o avoid returning immediately in this case it requires a minimum staying in adjustment to the radiant panels still given by Par43 65 Max staying time in dehumidification 4 11 CLIMATIC COMPENSATION It...

Page 33: ...oiler integration defrosting cycle water side or air side anti freeze heaters etc please refer to chillers and fancoils instructions manuals 4 14 SPECIAL FUNCTIONS From the main menu choosing the icon...

Page 34: ...unlock the screensaver set by default to 0 and modifiable by accessing to user s parameters see Paragraph 3 6 5 1 5 REMOTE ACCESS The device can interact with the local network by an Ethernet port acc...

Page 35: ...o shift to next available pages click on the links at the page bottom Figure 38 Touch Screen Ethernet Command page The commands present in the Command page are referred to the entire system The operat...

Page 36: ...t points set for the winter season water set point economy water set point and if enabled double set point second water set point and second water economy set point appear under Winter while under the...

Page 37: ...oard USB port For the upgrade copy the upgrade file in the main root of a USB pen drive insert the pen drive into the Touch Screen USB port enter into Configurations User s menu see Paragraph 3 6 5 1...

Page 38: ...C Heat 20 0 35 0 15 0 C 19 m5 comp Text FC 10 0 10 0 0 0 20 m6 comp Text FC 10 0 10 0 0 0 21 Set2 Text comp CHIL Cool 0 0 50 0 20 0 C 22 Set2 Text comp CHIL Heat 20 0 35 0 10 0 C 23 Second m1 comp Tex...

Page 39: ...um temp of the fancoils of the zone 2 Maximum temp of the fancoils of the zone 3 Temperature measured by the Touch Screen control panel 0 3 1 50 Regulation temperature in zone 5 Winter 0 Average temp...

Page 40: ...imum temp of the fancoils of the zone 2 Maximum temp of the fancoils of the zone 3 Temperature measured by the Touch Screen control panel 0 3 1 58 Regulation temperature in zone 4 Summer 0 Average tem...

Page 41: ...2 Maximum temp of the fancoils of the zone 3 Temperature measured by the Touch Screen control panel 0 3 1 63 Regulation temperature in zone 9 Summer 0 Average temp of the fancoils of the zone 1 Minim...

Page 42: ......

Page 43: ......

Page 44: ...printing errors It also reserves the right to modify its products as deemed necessary or useful without jeopardising their essential features 46033 casteldario mantova italia tel 39 0376 57001 fax 39...

Reviews: