33
Tec
hnical f
eatures and dimensions
Default
Individual values
Value range
Description
10 - 800 HOURS
SEQUENCE CHANGE
200 HOURS
00 min - 30 min
CYCLE BLOCK
00 min
00 - 01
BOILER COOLING FUNCTION
00
30°C - 120°C
BOILER COOLING TEMPERATURE
95
00 - 06
HS 1 TYPE
06
01 - 03
HS 2 STORAGE TANK
01 - 01 - 02
PUFFER
00, 01 (OFF - ON)
SCREED
00
00
00 OFF
00 - 04
HS 1 BUS
04
00 - 05
HS 2 TYPE
00
** see note
SCREED PROGRAM
2K - 20K<P>
HYSTERESIS BURNER 2
2K
* For only one modulating boiler, set the first stage value of the boiler at 1, in the second leave the dashes.
For two modulating boilers in cascade, set the first stage value at 1 for both boilers and in the second leave the dashes.
All other boiler stages must be disabled.
** See E8.5064 heating controller instruction manual
Default
Individual values
Value range
Description
DOMESTIC HOT WATER PRODUCTION
00 - 01 (OFF / ON)
CHARGE PUMP
01 (ON)
00 , 01, 02, 03
PARALLEL PUMP RUNNING
01
00K - 50K
T DHW
20K
5K - 30K
DHW HYSTERESIS
5 degrees
00 min - 30 min
DHW FOLLOWUP
00 min
00, 01 (OFF / ON)
THERMOSTAT INPUT
00 OFF
00, 01 (OFF / ON)
THERMOSTAT FUNCTION
00 OFF
Exit level using
RETURN
00, 01 (OFF / ON)
LOADING
00 OFF
Default
Individual values
Value range
Description
HEATING CIRCUIT 1
00 - 04
HEATING CIRCUIT FUNCTION
0
00 - 03
PUMP FUNCTION
0
5 - 25
MIXER OPEN
----
5 - 25
MIXER CLOSED
----
20 °C - 110 °C
MAX FLOW TEMPERATURE
95 °C
10 °C - 110 °C
MIN FLOW TEMPERATURE
30 °C
(-15)°C - (5)°C
FROST PROTECTION TEMP
0 ℃
0:00 - 24:00
OUTSIDE TEMP DELAY
0.00
00K - 50K
HEATING SLOPE DISTANCE
5 °C
00 - 01 (OFF / ON)
MANDATORY REDUCTION
01
Exit level using
RETURN
01 - 06
SEQUENCE MODE
01