PARAMETER HCM (BCM) MODULE
CODE
SYMBOL
PARAMETER DESCRIPTION
U.M.
RANGE
SETTING
FACTORY
MIN
MAX
803
Srv
Enabled services
0
3
3
483
rP
CH: Temp. Differenziale Max
°C
0,0
50,0
30,0
34
HY
Burner OFF hysteresis
°C
5,0
20,0
5,0
31
HL
CH: Setpoint min
°C
20,0
40,0
25,0
39
HH
CH: Setpoint max
°C
45,0
85,0
85,0
786
ES
Sensore Temp. Esterna
0
2
1
322
Po
Pump overrun time
min
1
10
5
341
PL
Pump minimum modulation level
Volt
0,0
10,0
3,0
313
Pr
Pump maximum modulation level
Volt
0,0
10,0
10,0
346
FL
Minimum relative fan speed
%
0,0
100,0
22,0
800
mB
Burners: Min. Insert
1
8
1
336
HS
Temperature control: slope limit.
°C/min
1
30
5
353
HP
Temperature control: proportional gain
°C
0
50
25
354
HI
Temperature control: integrative gain
0
50
12
478
Hd
Temperature control: derivative gain
0
50
12
816
MI
Modbus address
1
127
1
817
MT
Timeout Modbus
sec
0
240
180
896
TU
Temperature unit:
0
1
0
309
St
Application code:
0
1
0
Summary of Contents for ALKON 115 EXT
Page 10: ...10 2 3 DIMENSIONI VISTA FRONTALE VISTA DA SOTTO VISTA SUPERIORE VISTA LATERALE...
Page 36: ...36 4 5 SCHEMA ELETTRICO DI COLLEGAMENTO PRATICO...
Page 48: ...10 2 3 DIMENSIONS Front view View from below View from above Side view...
Page 57: ...19 E N G L I S H Installation Instructions 120 optional adapters for twin flue systems...
Page 73: ...35 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 74: ...36 4 5 WIRING DIAGRAM...
Page 78: ...40...
Page 79: ...41...