GENERAL INFORMATION

Any repairs must be performed solely by personnel authorised 

by Unical AG S.p.A., using original spare parts only. Failure to 

comply with the above can compromise the safety of the appli

-

ance and void the warranty. 

To  guarantee  appliance  efficiency  and  its  correct  operation, 

yearly maintenance must be performed by qualified personnel. 

Should you decide not to use the appliance, parts entailing 

potential sources of hazard must be made safe. 

Before commissioning an appliance that has not been used, 

wash the domestic hot water production system, making the 

water flow until it has been fully replaced.  

Should the appliance be sold or transferred to a new owner or 

if you move and leave the appliance, always make sure that the 

instruction booklet accompanies it in order to be consulted by 

the new owner and/or installer. 

Only original accessories must be used for all appliances with 

optionals or kits (including electric). 

This appliance is intended solely for the use for which it was 

expressly designed. 

Any other use is to be considered improper and therefore dan-

gerous (*).

1.1  - GENERAL  wARNINGs

T

he instruction booklet is an integral and essential part of the 

product and must be kept by the user. 

Read the warnings contained in this instruction booklet carefully 

as they provide important guidelines regarding installation, use 

and maintenance safety. 

Keep the booklet with care for further consultation. 

Installation and maintenance must be performed in compliance 

with the standards in force according to the instructions of the 

manufacturer, up to standard  and by personnel qualified and 

certified in compliance with law. 

Systems for the production of domestic hot water MUST be 

constructed entirely with compliant materials.

By professionally qualified personnel we mean: personnel with 

specific technical skill in the field of heating system components 

for civil use, domestic hot water production and maintenance. 

Personnel must have the qualifications provided for by current 

legislation. 

Incorrect installation or improper maintenance can cause dam-

age to persons, animals or objects for which the manufacturer 

is not responsible.

Before performing any cleaning or maintenance, disconnect the 

appliance from the energy mains by acting on the switch of the 

system and/or through the specific cut-off devices. 

Do not obstruct the terminals of the intake/exhaust ducts. 

In case of failure and/or malfunctioning of the appliance, switch 

it off and do not try to repair it or intervene on it directly. Contact 

only personnel qualified in compliance with law. 

Summary of Contents for ALKON 115 EXT

Page 1: ...E N G L I S H I TA L I A N O 115 EXT 130 EXT 140 EXT ISTRUZIONI PER L INSTALLATORE E IL MANUTENTORE INSTALLATION AND SERVICING MANUAL ALKON...

Page 2: ...smaltito come un rifiuto urbano Pu essere portato ad un centro speciale di riciclaggio gestito dall autorit locale o ad un rivenditore che offre questo servizio Lo smaltimento separato di un apparecc...

Page 3: ...ifica regolazione della pressione al bruciatore 25 Attenzione il presente manuale contiene istruzioni ad uso esclusivo dell installatore e o del manutentore professionalmente qualificato in conformit...

Page 4: ...parte integrante ed essenziale del prodotto e dovr essere conservato dall utente Leggere attentamente le avvertenze contenute nel libretto in quanto forniscono importanti indicazioni riguardanti la s...

Page 5: ...e le presenti istruzioni nonch gli altri documenti relativi all apparecchio inseriti nella busta contenuta nell imballo L utente deve custodire tale documentazione in modo da poterla avere a disposizi...

Page 6: ...alimentazione gas aria acqua e corrente elettrica al condotto fumi alla valvola di sicurezza e alla sua tubazione di scarico agli elementi costruttivi che influiscono sulla sicurezza operativa dell ap...

Page 7: ...EN13203 1 19 PMW Pressione max esercizio sanitario 20 T max Temperatura max sanitario C Caratteristiche elettriche 21 Alimentazione elettrica 22 Consumo 23 Grado di protezione D Paesi di destinazione...

Page 8: ...esta protezione puo intervenire solo se presenti alimentazione elettrica e gas Se una delle due viene a mancare e al ripristino 30 SMG rileva una temperatura tra 2 e 5 C l apparecchio si comporter com...

Page 9: ...A N O 2 2 VISTA INTERNA CON L INDICAZIONE DEI COMPONENTI PRINCIPALI 2 CARATTERISTICHE TECNICHE E DIMENSIONI 2 1 CARATTERISTICHE TECNICHE NOTA Maggiori info nella sezione Info Tecniche alla pagina del...

Page 10: ...10 2 3 DIMENSIONI VISTA FRONTALE VISTA DA SOTTO VISTA SUPERIORE VISTA LATERALE...

Page 11: ...fumi 20 Valvola di sicurezza 21 By pass automatico N U 22 rb SRR Sensore di temperatura ritorno 23 tf TLC Termostato di sicurezza collettore fumi N U 24 Scambiatore Condensatore in al luminio 25 Valv...

Page 12: ...DISPONIBILE La tabella fornisce indicativamente le portate del circolatore in funzione del t del circuito primario ALKON 115 EXT ALKON 130 EXT ALKON 140 EXT Potenza in kW 115 125 135 Portata massima i...

Page 13: ...peratura massima di funzionamento C 85 85 85 Portata massica fumi min kg h 12 58 17 8 12 58 Portata massica fumi max kg h 129 20 206 2 153 03 Eccesso aria 24 25 26 8 25 53 Perdite al camino con brucia...

Page 14: ...di bassa temperatura Tr 30 C P1 kW 20 5 40 4 23 7 Rendimento al 30 delle potenza termica nominale in regime di bassa temperatura Tr 30 C 1 97 6 97 1 97 6 Caldaia con regolazione range di potenza SI N...

Page 15: ...ia e camino canna fumaria Attenzione Se nel locale di installazione sono presenti polveri e o vapori aggressivi corrosivi l apparecchio deve essere adeguatamente protetto e deve poter funzionare indip...

Page 16: ...sone animali o cose suben tranti in seguito a mancata osservanza di quanto sopra esposto Nell imballo oltre all apparecchio contenuta la BUSTA DOCUMENTAZIONE con Libretto istruzioni d uso per responsa...

Page 17: ...produzione di acqua calda ventilazione camini idonei a scaricare i prodotti di combustione di caldaie a condensazione e quant altro applicabile Nella scelta del luogo di installazione dell apparecchi...

Page 18: ...o SINGOLO 120 DA m FINO A m 1 20 Collegamento ad un condotto di evacuazione dei prodotti della combustione verso l esterno del lo cale l aria comburente prelevata direttamente nell ambiente dove l app...

Page 19: ...19 Istruzioni per l installazione I TA L I A N O Adattatori 120 opzionali per sistemi sdoppiati...

Page 20: ...costruttore non pu essere considerato responsabile Avvertendo odore di gas a Non azionare interruttori elettrici il telefono o qualsiasi altro oggetto che possa provocare scintille b Aprire immediatam...

Page 21: ...hiuso il rubinetto di intercettazione impianto posto sotto al circolatore L impianto deve essere dotato di un proprio rubi netto di svuotamento di dimensione adatta alla capacit dell impianto stesso L...

Page 22: ...to SICUREZZE 42 eBUS Morsetti collegamento eBUS 43 BCM Controllore di cascata 44 F1 Fusibile Alimentazione 6 3 A 45 F2 Fusibile Alimentazione 6 3 A 46 INT C1 Interruttore Inibizione Corpo 1 47 INT C2...

Page 23: ...ttuato a regola d arte come previsto dalle vigenti norme Si ricorda che necessario installare sulla linea di alimentazione elettrica della caldaia un interruttore bipolare con distanza tra i contatti...

Page 24: ...24 NOTA Maggiori info nella sezione Info Tecniche alla pagina della caldaia nel sito www unicalag it Pannello comandi in remoto...

Page 25: ...nsa stato riempito d acqua come indicato al capitolo 3 7 eventuali saracinesche di intercettazione impianto sono aperte il gas da utilizzare corrisponde a quello di taratura della caldaia in caso cont...

Page 26: ...a C e confermare con tasto A inserire codice d accesso 3 MASSIMA MINIMA POTENZA Posizionarsi con manopola C su Confermare con il tasto A viene visualizzato Posizionarsi con manopola C su Confermare co...

Page 27: ...lla MINIMA PO TENZA vedi 3 11 1 Una volta che il bruciatore acceso controllare che il valore CO2 alla potenza MINIMA corrisponda a quello indicato nella tabella UGELLI PRESSIONI Correggere eventualmen...

Page 28: ...9 1 9 2 45 Gas nat G25 25 9 22 83 9 1 9 2 45 Propano G31 37 9 20 78 11 10 9 45 ALKON 130 Tipo di Gas Press Aliment Ugelli Diaframma collettore Velocit ventilatore Livelli CO2 Potenza avviam mbar mm n...

Page 29: ...aldamento nonch la valvola di entrata dell acqua fredda se chiuse in preceden za Sfiatare e se necessario procedere al ripristino della pres sione dell impianto di riscaldamento fino a raggiungere una...

Page 30: ...anza acqua 13 Il pressostato blocca la caldaia se la pressione d acqua inferiore a 0 4 bar Senza richiesta chiudere i rubinetti di intercettazione del circuito di riscalda mento aprire il rubinetto di...

Page 31: ...ione dell ap parecchio il serbatoio del gas sia stato disa erato Per una disaerazione a regola d arte del serba toio rivolgersi al fornitore dei gas liquido e co munque a personale abilitato ai sensi...

Page 32: ...edere alla programmazione tecnica di ogni dispositi vo richiesta password 0000 4 SELEZIONE Selezionare il parametro con manopola C Premere il tasto A selez 5 MODIFICA Ruotare manopola C per modificare...

Page 33: ...ensione 0 100 45 314 Sb Modulazione in Standby 0 100 26 319 FH Modulazione Massima 0 100 95 346 FL Modulazione Minima 0 100 22 2590 Potenza del Bruciatore kW 1 1000 70 483 rP Gen Temp Differenziale Ma...

Page 34: ...Sensore Temp Esterna 0 2 1 322 Po Pompa Postcircolazione min 1 10 5 341 PL Pompa Comando Minimo Volt 0 0 10 0 3 0 313 Pr Pompa Comando Massimo Volt 0 0 10 0 10 0 346 FL Modulazione Minima 0 0 100 0 2...

Page 35: ...35 Istruzioni per l installazione I TA L I A N O QUESTA PAGINA E LASCIATA INTENZIONALMENTE IN BIANCO...

Page 36: ...36 4 5 SCHEMA ELETTRICO DI COLLEGAMENTO PRATICO...

Page 37: ...disposizione collegamento pressostato differenziale PPD2 PF Pressostato Fumi PPD1 PV1 Pressostato Ventilatore 1 versione Australia PPD2 PV2 Pressostato Ventilatore 2 versione Australia PR Pulsante di...

Page 38: ...mma parassita 12 SENSORE RISCALDAMENTO 11 Avaria al sensore riscaldamento Verificare l efficienza del sensore vedi tabella Res Temp Par 4 o i suoi collegamenti 14 SONDA DI RITORNO Sensore SRR ausiliar...

Page 39: ...effetto stop Tentare un Reset poich il sistema automaticamente aziona la funzione di antigelo e quindi potrebbe trattarsi solo di un avviso 18 Protezione massima t manda ta ritorno effetto stop Contro...

Page 40: ...ocal authorities or to a dealer who offers this service Separate disposal of a domestic appliance avoids possible negative consequences for the environment and human health deriving from inappropriate...

Page 41: ...ction 18 3 7 Connections 20 3 8 Filling the system 21 3 9 Electrical connections 22 3 10 Commissioning 25 3 11 Measurement of combustion efficiency during installation 26 3 11 1 Calibration function a...

Page 42: ...t and must be kept by the user Read the warnings contained in this instruction booklet carefully as they provide important guidelines regarding installation use and maintenance safety Keep the booklet...

Page 43: ...onsultation Inform the user about the importance of the air vents and the flue gas exhaust system highlighting their essential features and the absolute prohibition of modifying them Inform the user c...

Page 44: ...e Do not modify the following parts the boiler the gas air water and electricity supply lines the flue gas pipe the safety valve and the exhaust pipe the construction parts which affect the operating...

Page 45: ...rcuit characteristics 9 Pn Effective nominal output 10 Pcond Effective output in condensation 11 Qn Maximum heat output 12 Adjusted Qn Adjusted for rated heat output 13 PMS Max heating operating press...

Page 46: ...ss fr 9 15 NOTE Further details in the section Technical Information on the boiler indicated at page 2 This protection can intervene only if the electricity and gas supplies are connected If one of th...

Page 47: ...L I S H 2 2 VIEW WITH THE INDICATION OF THE MAIN COMPONENTS 2 TECHNICAL FEATURES AND DIMENSIONS 2 1 TECHNICAL FEATURES NOTE Further details in the section Technical Information on the boiler page of t...

Page 48: ...10 2 3 DIMENSIONS Front view View from below View from above Side view...

Page 49: ...S PV Flue gas pressure switch 20 Safety valve 21 Automatic by pass N U 22 rb SRR Return temperature sensor 23 tf TLC Flue gas collector safety thermo stat N U 24 Aluminium Heat Exchanger Capacitor 25...

Page 50: ...m c a metres of water The table provides an indication the flow the pump in function of the Dt of the primary circuit ALKON 100 EXT ALKON 115 EXT ALKON 140 EXT Power supply in kW 100 115 135 Max flow...

Page 51: ...rating temperature C 85 85 85 Flue gas mass flow rate min kg h 12 58 12 58 12 58 Flue gas mass flow rate max kg h 114 39 129 20 153 03 Excess air 26 84 24 25 25 53 Flue losses with burner in operation...

Page 52: ...utput in low temperature regime Tr 30 C P1 kW 18 20 5 23 7 Useful efficiency at 30 of nom heat output in low temperature regime Tr 30 C 1 97 5 97 6 97 6 Range rated boiler YES NO SI SI SI Auxiliary el...

Page 53: ...ention If there is dust and or if there are aggressive corrosive vapours present in the installation room the appliance must be protected suitably and must be able to operate independently from the ai...

Page 54: ...sons animals or objects due to failure to comply with the instruction above As well as the appliance the packaging contains A DOCUMENTATION ENVELOPE User operating instructions booklet Instruction boo...

Page 55: ...ntilation chimneys suitable to discharge the products of combustion of condensing boilers and everything else applicable When choosing the place of the installation of the appliance follow the safety...

Page 56: ...AME 2 optional B23P TOTAL LENGTH LS SINGLE 120 FROM m TO m 1 20 Connection to a combustion products evacuation pipe outside the room the combustion air is taken directly from the room where the applia...

Page 57: ...19 E N G L I S H Installation Instructions 120 optional adapters for twin flue systems...

Page 58: ...ts for which the manufacturer cannot be held responsible If you smell gas a Do not operate electric switches the telephone or any other object that may cause sparks b Immediately open doors and window...

Page 59: ...ke sure that drain valve 29 it is closed The system must be equipped with its own drain valve with a size suitable to the capacity of the system Pressure in the mains supply must be between 0 5 and 6...

Page 60: ...on SAFE terminal 42 eBUS eBUS conenction 43 BCM Burner Control Manager Cascade controller 44 F1 Power Fuse 6 3 A 45 F2 Power Fuse 6 3 A 46 INT C1 Switch Inhibit Body 1 47 INT C2 Switch Inhibit Body 2...

Page 61: ...red the regulations in force Remember that a bipolar switch must be installed on the boiler power line with over 3 mm between contacts easy to access making maintenance quick and safe The power cable...

Page 62: ...24 Control panel remotely NOTE For more information See Technical Info from site indicated at pag 2...

Page 63: ...valves open does the gas to be used correspond to the boiler calibration gas otherwise perform the boiler conversion in order to use the gas available see section 4 3 this operation must be carried o...

Page 64: ...r Mode Place on with knob C and confirm with A Insert acces code 0000 3 MAXIMUM MINIMUM POWER Place with knob C on Confirm with button A display shows Place with knob C on Confirm with button A with k...

Page 65: ...burner is on check that the CO2 MINIMUM value corresponds to that indicated in the table NOZZLES PRES SURE Correct it if needed by turning with a screwdriver the screw R CLOCKWISE to increase it ANTI...

Page 66: ...hing off the main switch For proper operation the CO2 values must be calibrated with particular attention observing the values indicated in the table close the flue gas inspection sample points of the...

Page 67: ...nlet valve if closed previously Vent and if necessary restore the heating pressure until reaching a pressure of 0 8 1 0 bar Open the gas shut off valve Switch the boiler on Make sure the appliance is...

Page 68: ...safety pressure switch against water deficiency 13 Does the pressure switch block the boiler if the water pressure is below 0 4 bar Without request close the shut off valves of the heating circuit ope...

Page 69: ...e sure that the gas tank has been deaer ated before installing the appliance For state of the art deaeration of the tank contact the LPG supplier or a person qualified in compliance with law If the ta...

Page 70: ...d push buton A to enter in programming list for each device requires password 0000 4 SELECTION Selection parameter with knob C Push button A select 5 MODIFY Turn knob C to modify value Push button A s...

Page 71: ...tion 0 100 45 314 Sb Relative fan speed at burner standby 0 100 26 319 FH Maximum relative fan speed 0 100 95 346 FL Minimum relative fan speed 0 100 22 2590 Burner maximum capacity kW 1 1000 70 483 r...

Page 72: ...run time min 1 10 5 341 PL Pump minimum modulation level Volt 0 0 10 0 3 0 313 Pr Pump maximum modulation level Volt 0 0 10 0 10 0 346 FL Minimum relative fan speed 0 0 100 0 22 0 800 mB Burners Min I...

Page 73: ...35 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 74: ...36 4 5 WIRING DIAGRAM...

Page 75: ...D1 NOT USED M5 Terminal for pressure switch 2 PPD2 NOT USED PF Flue gas pressure switch PPD1 PV1 Fan pressure switch NOT USED PPD2 PV2 Fan pressure switch NOT USED PR Reset button SMG Sensor Flow gene...

Page 76: ...on flame parasite 12 HEATING SENSOR 11 Heating sensor fault Check the efficiency of the sensor see table Res Temp Par 4 or its connections 14 RETUR HEATING SENSOR Auxiliary SRR sensor interrupted Chec...

Page 77: ...function of antifreeze and then it may be only a warning 18 Maximum protection Dt flow and return Status stop Control of the circulation verify installation 19 OVERHEATING OF CH FLOW Overheating of t...

Page 78: ...40...

Page 79: ...41...

Page 80: ...i di trascrizione o di stampa Si riserva altres il diritto di apportare ai propri prodotti quelle modifiche che riterr necessarie o utili senza pregiudicarne le caratteristiche essenziali Unical decli...