OPM1
EXAMPLE 4:
MULTIMODE FIBER, POINT-TO-POINT, 1 JUMPER
Fiber Type
Connectors Used
Test Jumper Setup
OPM Used
OLS Used
Multimode
LC
(1) Simplex SC/LC
OPM1
LSMM
Page 3
M-UM038-01 RP 460 Reference and Test
DMT
Example 1: Singlemode Fiber, Point-to-Point, 1 Jumper
Fiber Type
Singlemode
Connectors Used
LC
Test Jumper Setup
Single
OPM Used
RP 460
OLS Used
DLS 355
Fiber-Under-Test
The fiber-under-test is singlemode with LC
connectors on each end. The fiber-under-test may
be up to 250 kilometers long. In this example, the
fiber-under-test is 400 meters long.
Test Jumper
The test jumper is a one-meter singlemode fiber
with SC and LC connectors. The SC connector will
be plugged into the DLS 355 laser source and the
LC connector will be used to interface with the
fiber-under-test.
Power Meter
The RP 460 power meter is set to the
1550nm wavelength. The 1310nm
wavelength may also be used. Always
match the wavelength on the RP 460
to the wavelength on the DLS 355. The
adapter on the RP 460 is the AC 029 LC
adapter.
Light Source
The DLS 355 laser source is set to the
1550nm wavelength. The 1310nm
wavelength may also be used. The
adapter is the default AC 022B SC adapter.
400m Fiber
1m Jumper
The fiber-under-test is multimode with LC connectors on
each end. In this example, the fiber-under-test is
400 meters long.
TEST JUMPER
The test jumper is a one-meter multimode fiber with SC
and LC connectors. The SC connector will be plugged
into the LSMM LED source and the LC connector will be
used to interface with the fiber-under-test.
POWER METER
The OPM1 power meter is set to the 850nm
wavelength. The 1300nm wavelength may also be
used. Always match the wavelength on the OPM1 to
the wavelength on the LSMM. The adapter on the OPM1
is the OPAL LC adapter.
LIGHT SOURCE
The LSMM LED source is set to the 850nm
wavelength. The 1300nm wavelength may also be
used. The adapter is the default OPAS SC adapter.
FIBER-UNDER-TEST
Page 9
M-UM038-01 RP 460 Reference and Test
DMT
Example 4: Multimode Fiber, Point-to-Point, 1 Jumper
Fiber Type
Multimode
Connectors Used
LC
Test Jumper Setup
Single
OPM Used
RP 460
OLS Used
DLS 350
Fiber-Under-Test
The fiber-under-test is multimode with LC
connectors on each end. In this example, the
fiber-under-test is 400 meters long.
Test Jumper
The test jumper is a one-meter multimode fiber
with SC and LC connectors. The SC connector will
be plugged into the DLS 350 LED source and the
LC connector will be used to interface with the
fiber-under-test.
Power Meter
The RP 460 power meter is set to
the 850nm wavelength. The 1300nm
wavelength may also be used. Always
match the wavelength on the RP 460
to the wavelength on the DLS 350. The
adapter on the RP 460 is the AC 029 LC
adapter.
Light Source
The DLS 350 LED source is set to the
850nm wavelength. The 1300nm
wavelength may also be used. The
adapter is the default AC 022B SC adapter.
400m Fiber
1m Jumper
Summary of Contents for TEK-3
Page 2: ...SECTION ONE LSMM LED LIGHT SOURCE QUICK START GUIDE NORTH AMERICA ...
Page 8: ...SECTION TWO LSMM LED LIGHT SOURCE TECHNICAL GUIDE NORTH AMERICA ...
Page 11: ...SECTION THREE OPM1 OPTICAL POWER METER QUICK START GUIDE NORTH AMERICA ...
Page 18: ...SECTION FOUR OPM1 OPTICAL POWER METER REFERENCE TEST GUIDE NORTH AMERICA ...