Page 16 

Initial Installation Procedure 

 

printed: 06/2020  Subject to change! 

:FFUserManual.docx 

4.4.2  Control of nominal heat load 

Firstly, please check whether the unit is adjusted for the existing kind of gas. For this you have to 

check whether the indication on the type plate corresponds to the existing kind of gas. If you adjust 

the unit for other gas types please check the indication of the nozzles. The nominal heat load re-

sults from using the right nozzle with connection pressure of 

+ 20 mbar with natural gas H and natural gas L (for France E+) 
+ 50 mbar with LPG

 

by taking effect of the corresponding nozzle area. 

The permission of operation with the resulting nominal heat load under dependency of the planned 

nozzles results from the following connection pressure bounds: 

15 to 25 mbar with natural gases) 
25 to 35 mbar and 42.5 to 57.5 mbar with LPG

 

Starting the operation outside these pressure bounds is not permitted. 

The connection pressure is measured by a pressure gauge (indication exactness: 0.1 mbar). For 

this the sealing screw in the connection pressure measuring socket of the main gas supply has to 

be loosened and the pressure gauge has to be connected. 

4.4.3  Checking of nominal heat load with LPG 

Check whether the indication of used nozzles corresponds to the indications of the manufacturer. 

Secure that the existing low-pressure regulator on site does not exceed a maximum output pres-

sure of 50 mbar according to section 4.4.2 (control of type plate or pressure measurement). 

4.4.4  Control of function 

  Set the unit into operation according to the manual. 

  Check the unit for gas leaks. 

  Check the correct adjustment of primary air and nozzles (pilot flame device, main nozzles (at 

the burner nozzle assembly), minimum adjustment nozzles (at the all gas valve). 

  Check the transmission ignition and regularly flames of the burners with minimum and maximum 

adjustment. 

  A maintenance contract is recommended. 

4.5  Re-adjustment 

Attention! 

 Before any re-adjustment works at the unit are executed the main gas supply 

has to be closed and the unit has to be unplugged firstly. 

 

All units of our production are single examined and are adjusted for the kind of gas required by the 

customer. If no indication has been made, the units are principally adjusted for LPG. If the unit is to 

be re-adjusted it has to be observed that this is made by an approved technician or by the Ubert 

service technicians. The corresponding nozzles sizes are to be find in the nozzle table. For re-ad-

justment the following measures have to be made: 

 

  Replacement of pilot flame nozzles. 

  Replacement of main nozzles. 

  Replacement of bypass nozzle 

  Adjustment of primary air. 

  Checking of function and indication of new gas type on the type plate at the front of the unit. 

4.5.1  Replacement of pilot flame nozzle (pilot flame device) 

  Close the main gas supply and unplug the unit. 

  Remove the side walls after unscrewing them. 

  Remove the ignition cable from the ignition plug at the pilot flame. 

  Unscrew the ignition plug from the pilot flame device. 

  Unscrew the gas supply connected to the pilot flame device. 

  Remove the thermo feeler. 

Summary of Contents for FF Series

Page 1: ...User Manual Wall of Flame FF Series...

Page 2: ......

Page 3: ...ata 8 4 Initial Installation Procedure 14 4 1 Unpacking 14 4 2 Installation 14 4 3 Electrical connection 15 4 4 Gas connection 15 4 5 Re adjustment 16 4 6 Waste Water Connection 17 4 7 Preparation of...

Page 4: ...following That they know about the basic safety instructions and do know the regulations how to prevent possible accidents That they have read the safety chapter and warnings in this operation manual...

Page 5: ...on regular maintenance of any parts being subject to wear and tear In case of nonprofessional service In case of any force majeure 2 3 Explanation of Symbols and notes for the user Within this operati...

Page 6: ...are only allowed to operate the unit under supervision of a trained and experienced person 2 5 4 Operating the controls Only trained personnel is allowed to operate the controls 2 5 5 Safety check du...

Page 7: ...the manufacturer Never weld on load bearing parts of construction All reconstructions do require a written permission of the manufacturer Improper parts have to be changed immediately Only use origin...

Page 8: ...al effect by glowing glass filaments Illumination by halogen light 3 3 Technical Data 3 3 1 Capacity Depending on the size up to 6 chickens per spit 3 3 2 Dimensions mm Model W x H x D Number of Spits...

Page 9: ...able FF 28 LPG 50mbar 4 130 80 screwed tightly open 20 screwed tightly FF 28 LPG 30mbar 4 140 90 screwed tightly open 20 screwed tightly FF 28 Natural gas H 4 240 50 adjustable open 35 adjustable FF 2...

Page 10: ...F 44 Natural gas H 4 240 50 adjustable open 35 adjustable FF 44 Natural gas L 4 260 50 adjustable open 35 adjustable FF 44 Natural gas E 4 240 50 adjustable open 35 adjustable FF 46 LPG 50mbar 6 130 8...

Page 11: ...s L 30 9 12 3 69 FF 26 Natural gas E 20mbar 30 8 48 3 17 FF 26 Natural gas E 25mbar 27 7 3 17 FF 28 LPG 40 13 87 3 15 FF 28 Natural gas H 40 11 31 4 23 FF 28 Natural gas L 40 12 16 4 93 FF 28 Natural...

Page 12: ...ural gas L 60 18 24 7 38 FF 46 Natural gas E 20mbar 60 16 96 6 34 FF 46 Natural gas E 25mbar 54 14 6 34 FF 48 LPG 80 27 74 6 3 FF 48 Natural gas H 80 22 62 8 46 FF 48 Natural gas L 80 24 32 9 86 FF 48...

Page 13: ...Power kW Electrical connection V N Hz 0085 Differing from a m indications the type plate will be executed suitable for the following countries Netherlands for natural gas L connection pressure 25 mba...

Page 14: ...y that the surrounding area can be cleaned 4 2 2 Place of operation Attention The device must be placed on a level solid and fireproof surface in an well ventilated room under an on site extraction ho...

Page 15: ...cal and technical data of your unit from the nameplate The unit is ready for plug in For power supply a shockproof socket is necessary Make sure the supply cable is protected separately with 16 Amps T...

Page 16: ...2 control of type plate or pressure measurement 4 4 4 Control of function Set the unit into operation according to the manual Check the unit for gas leaks Check the correct adjustment of primary air a...

Page 17: ...the ignition cable from all piezo ignitors Remove the front operation panel carefully after unscrewing it The minimum adjustment nozzle is to be find at the upper front side of the all gas valve Unsc...

Page 18: ...taking up the grill products 2 Fat Drawer catches the meat juice and fat coming out of the grill product 3 Gear chain sets the spit in rotation 4 Spit support used as outer support of spit 5 Control k...

Page 19: ...the key of the piezo igniter After the ignition still push the knob for approx 15 20 seconds For minimum adjustment you have to turn the knob counter clockwise Turn the knob on position 0 in order to...

Page 20: ...ade steel machine working always keep the high grade steel surface clean watch out that there is always enough fresh air on the surface never contact the surface with rusty material never use bleachin...

Page 21: ...ageous anti corrosive properties The corrosion resistance of the rustproof steel has a passive layer which can be formed on the surface by oxidation The oxygen in the air is enough to form a passive l...

Page 22: ...f natural plastic or stainless steel bristles for mechanical cleaning Steel wool or brushes with unalloyed steel lead to external rust caused by abrasion Fresh rust spots can be removed with mild acti...

Page 23: ...nd the bottom plate Remove the ignition cable from the piezo igniter You can remove and replace the piezo igniter by loosening the fixing nut from the front panel The re installation is to be made in...

Page 24: ...rsed sequence 6 5 7 Motor Remove the lower fat drawer and the bottom plate Loosen the 2 screws from the protection plate above the motor and remove it Unplug the motor Loosen the chain tension union f...

Page 25: ...its Spit does not rotate motor is not switched on Protective circuit breaker has re leased motor is defect Switch on the motor Push the protective circuit breaker gear 1 x Call the service Illuminatio...

Page 26: ...r piezo ignitor 1 3m 180710 1 ignition cable for piezo ignitor 1 75m 180711 1 FF26 Description Part No Amount scale light motor 360203 2 scale gas valve 360215 3 drive shaft 180596 1 burner 180590 3 c...

Page 27: ...ng drive shaft 380601 4 ignition cable for piezo ignitor 1 3m 180710 1 ignition cable for piezo ignitor 1 75m 180711 1 ignition cable for piezo ignitor 2 2m 180712 1 ignition cable for piezo ignitor 2...

Page 28: ...1 3m 180710 2 ignition cable for piezo ignitor 1 75m 180711 2 ignition cable for piezo ignitor 2 2m 180712 2 FF38 Description Part No Amount scale light motor 360203 2 scale gas valve 360215 8 drive s...

Page 29: ...1 3m 180710 2 ignition cable for piezo ignitor 1 75m 180711 2 FF46 Description Part No Amount scale light motor 360203 2 scale gas valve 360215 6 drive shaft 180597 1 burner left 180590 6 cast iron fi...

Page 30: ...m 352327 2 temperature probe M8 850mm 352328 2 temperature probe extension M8 M10 600mm 352329 6 switch element for push button 380242 1 push button 380244 1 ignition transformer 380260 1 pilot flame...

Page 31: ...Maintenance 31 printed 06 2020 Subject to change FFUserManual docx 6 9 Declaration of Conformity...

Reviews: