39
103536-08 - 4/18
Figure 23: Single Pipe Oil Line
A.
GENERAL
1. Use flexible oil line(s) so the burner swing door
can be opened without disconnecting the oil
supply piping.
2. A supply line fuel oil filter is recommended as a
minimum for all firing rates but a pleated paper
fuel oil filter is recommended for the firing rates
below 1.0 gph to prevent nozzle fouling.
3. Use Flared fittings only. Cast iron fittings
cannot be used.
4. Use of a high efficiency micron filter (Garber or
equivalent) in addition to a conventional filter is
highly recommended.
5. Piping used to connect the oil burner to the oil
supply tank shall not be smaller than 3/8" iron
pipe or 3/8" OD copper tubing. Copper tubing
shall have a .032" minimum wall thickness.
B.
SINGLE PIPE OIL LINES
1. Standard burners are provided with single-
stage 3450 rpm fuel units with the bypass plug
removed for single-pipe installations.
2. The single-stage fuel unit may be installed
single-pipe with gravity feed or lift. Maximum
allowable lift is 8 feet. See Figure 23.
3. Fuel Oil Line Deaerator – On many occasions
a leaky oil delivery line can introduce air
into the fuel oil supply system. This often
creates a rough starting condition and can
create a burner lockout state. In addition to
fixing the leak, a fuel line deaerator can be
installed to eliminate air. The single line from
the fuel tank is connected to the deaerator.
The burner pump must be connected to the
deaerator as a two pipe system. Follow the
oil pump manufacturer’s recommendations for
conversion to a two pipe system.
NOTICE
Do not use compression fittings.
Oil piping must be absolutely airtight or leaks
or loss of prime may result. Bleed line and
fuel unit completely.
Refer to your local jurisdictions regarding
any special considerations for fuel supply
requirements. In addition, refer to NFPA 31,
Standard for the installation of Oil-Burning
Equipment.
Under no circumstances can
copper with sweat style connectors be used.
WARNING
NOTICE
Some jurisdictions require the use of
a fusible shutoff valve at the tank and/or the
burner. In addition, some jurisdictions require
the use of a fusible electrical interlock with
the burner circuit. Check your local Codes for
special requirements.
•
•
Section VII: Oil Piping
Summary of Contents for MegaSteam MST288
Page 54: ...54 103536 08 4 18 Bare Boiler Assembly Section XII Repair Parts continued...
Page 56: ...56 103536 08 4 18 Bare Boiler Assembly Section XII Repair Parts continued...
Page 58: ...58 103536 08 4 18 Jacket Assembly Section XII Repair Parts continued...
Page 62: ...62 103536 08 4 18 Beckett AFG Burner Section XII Repair Parts continued...
Page 65: ...65 103536 08 4 18...
Page 66: ...66 103536 08 4 18...
Page 67: ...67 103536 08 4 18...