background image

TFP910

Page 4 of 20

Operation

When the fire protection system is ini-

tially pressurized, water flows into the 

system until the water supply and sys-

tem pressure become equalized, and 

the torsion Spring closes the Water-

way Clapper in the Alarm Check Valve. 

Once the pressures stabilize, the Alarm 

Check Valve is in service and the cen-

trally located groove in the Seat Ring is 

sealed. Consequently, with the Alarm 

Check Valve set for service, there is 

no flow through the alarm port to the 

alarm devices (i.e., water motor alarm 

and/or pressure alarm switch).
When there is a steady flow of water 

into the sprinkler system due to a sprin-

kler operation, the Waterway Clapper 

opens as shown in Figure 2. Water is 

then permitted to flow into the centrally 

located groove in the Seat Ring and 

out through the alarm port towards the 

Restriction Assembly (Figure 3). When 

the flow through the Inlet Restriction of 

the Restriction Assembly exceeds the 

flow through the Outlet Restriction, the 

Retard Chamber (where provided for 

systems with variable pressure), begins 

to fill.
Subsequently, the Water Motor Alarm 

and/or the pressure alarm switch will 

be actuated. The alarms will continue 

to be actuated as long as the Water-

way Clapper remains open. Water in 

the alarm lines will automatically drain 

out through the 1/8 inch (3,2 mm) Drain 

Orifice in the Restriction Assembly 

(Figure 3) when the Waterway Clap-

per closes (due to a stop in the flow of 

water into the sprinkler system).
For variable pressure systems, slow 

as well as small transient increases in 

water supply pressure may continue to 

build up in the system (via the Bypass 

Check Valve) without opening the 

Waterway Clapper.
A transient surge in supply pres-

sure that is sufficient only to open the 

Waterway Clapper momentarily will not 

cause a false alarm, and a portion of 

the increase in pressure will be trapped 

within the system, thus reducing the 

possibility of another opening. Any 

water in the alarm line is automatically 

drained, further reducing the possibil-

ity of a false alarm due to a successive 

transient surge in supply pressure.

Design 

Criteria

In planning installation of the TYCO 

Model AV-1-300 Alarm Check Valves, 

consideration must be given to the dis-

posal of the large quantities of water 

that may be associated with draining 

the system or performing a flow test.

Valves installed in the vertical position 

must have the flow going up. Valves 

installed in the horizontal position must 

be positioned so that the drain connec-

tion points down.
The sprinkler system designer must 

be aware that the configuration of 

the piping network and its tendency 

to trap pockets of air (such as in the 

case of a peaked-roof gridded sys-

tem) can affect the performance of the 

alarm system. Although a slight amount 

of trapped air is desirable to prevent 

significant pressure increases due to 

thermally induced expansion of the 

water, a large quantity of trapped air in 

a system may result in the possibility of 

an intermittent alarm.

The possibility of an intermittent alarm 

condition is a consequence of the fact 

that the flow out of the system through 

the test valve or a single sprinkler is 

very small relative to the flow that can 

be passed through the valve. This dif-

ference increases with valve size. If the 

system were free of trapped air, flow in 

would equal flow out and the Waterway 

Clapper would always stabilize at some 

open position (as needed to accommo-

date the required flow). With trapped 

air in the system, however, the Water-

way Clapper first opens wider since the 

system initially demands greater flow 

until the air pockets are compressed 

(back to nearly the supply pressure), 

and then it will tend to return closer 

PRESSURE

WATERFLOW

ALARM SWITCH

MOTOR ALARM

VALVE

RESTRICTION

(3,2 mm)

OUTLET

ORIFICE

RETARD CHAMBER

BEGINS TO FILL

INLET EXCEEDS OUTLET,

RESTRICTION ASSEMBLY

WHEN FLOW THROUGH

ASSEMBLY

1/8"

CHAMBER

RETARD

INLET

ALARM PORT

RING GROOVE AND

THROUGH SEAT

WATERFLOW

MAIN

DRAIN

ALARM ACTUATE

WATERFLOW PRESSURE

CHAMBER OVERFLOWS,

ONCE RETARD

WATER MOTOR

ALARM SWITCH AND

WATERFLOW

TO SYSTEM

WATERFLOW

TO WATER

7/32"

ORIFICE

(5,6 mm)

UPON SPRINKLER

FLOW, WATERWAY

CLAPPER OPENS

GAUGE

GAUGE

SUPPLY

PRESSURE

PRESSURE

SYSTEM

CHECK

VALVE

ALARM

SCREEN

DRAIN RESTRICTION

WITH 0.125" (3,2 mm)

ORIFICE

INLET RESTRICTION

WITH 0.219" (5,6 mm)

ORIFICE

FIGURE 2 

2-1/2, 4, 6 & 8 INCH (DN65, DN100, DN150 & DN200) 

MODEL AV-1-300 ALARM CHECK VALVE 

OPERATION

FIGURE 3 

RESTRICTION ASSEMBLY 

(Provided with Alarm Check Valve Trim)

Summary of Contents for AV-1-300

Page 1: ...herein must be installed and maintained in com pliance with this document as well as with the applicable standards of the National Fire Protection Association NFPA in addition to the standards of any...

Page 2: ...es 4 6 8 Inch NR Clapper See b 92 200 1 423 92 200 1 623 92 200 1 823 Hex Bolt Handhole Cover 2 1 2 Inch Valve x 1 1 4 Long CH DESCRIPTION REF VALVE PARTS 1 2 13 UNC 2A 6 Inch Valve x 1 3 4 Long CH 1...

Page 3: ...95 0 0 91 23 0 11 42 290 0 5 50 139 7 0 75 19 0 5 00 127 0 5 51 140 0 0 87 22 0 0 71 18 0 0 71 18 0 0 87 22 0 0 87 22 0 0 71 18 0 0 75 19 0 4 Inch DN100 6 Inch DN150 8 Inch DN200 2 1 2 Inch DN65 4 8 8...

Page 4: ...e TYCO Model AV 1 300 Alarm Check Valves consideration must be given to the dis posal of the large quantities of water that may be associated with draining the system or performing a flow test Valves...

Page 5: ...ch line at the point most remote from the alarm valve The vent line should be connected to the top of a cross main or to the end of a branch line and be located at the highest level of a multi level i...

Page 6: ...ple 1 4 x 2 1 2 Nipple CH DESCRIPTION 1 1 4 INCH NPT CONNECTION TO DRAIN 1 2 INCH NPT CONNECTION FOR WATERFLOW PRESSURE ALARM SWITCH RESTRICTION ASSEMBLY SEE FIGURE 3 3 4 INCH NPT CONNECTION FOR WATER...

Page 7: ...2 1 2 x 4 1 2 All Fittings and Nipples are galvanized Standard Order Install subassemblies in alphabetical order NOTES 3 1 2 CH Common Hardware 2 INCH NPT CONNECTION TO DRAIN 1 2 INCH NPT CONNECTION...

Page 8: ...ESCRIPTION CH CH CH CH CH CH P N CH 1 2 x 1 2 x 3 4 Tee All Fittings and Nipples are galvanized Standard Order Install subassemblies in alphabetical order NOTES 3 1 2 CH Common Hardware 2 INCH NPT CON...

Page 9: ...6 048 1 007 92 304 1 017 P N 1 4 90 Elbow 1 4 Plug CH CH All Fittings and Nipples are galvanized Standard Order CH Common Hardware NOTES 1 2 SUPPORT BRACKET SUPPORT BAR EXTERNAL BY PASS TUBE ALARM TES...

Page 10: ...ommon Hardware Select Appropriate Nipple Sizes per AV 1 Alarm Check Valve Size 4 Inch DN100 29 1 2 x 1 1 2 30 1 2 x 3 1 2 Nipple Number 1 2 x 2 1 2 1 2 x 4 1 2 6 Inch DN150 2 INCH NPT CONNECTION TO DR...

Page 11: ...3 4 Tee 1 2 x 1 1 2 Nipple CH All Fittings and Nipples are galvanized Standard Order Install subassemblies in alphabetical order NOTES 3 1 2 CH Common Hardware DRIP FUNNEL 2 INCH NPT CONNECTION TO DRA...

Page 12: ...TION TO DRAIN 1 2 INCH NPT CONNECTION FOR WATERFLOW PRESSURE ALARM SWITCH RESTRICTION ASSEMBLY SEE FIGURE 3 3 4 INCH NPT CONNECTION FOR WATER MOTOR ALARM 3 4 INCH NPT CONNECTION FOR WATER MOTOR ALARM...

Page 13: ...CH CH CH CH CH CH CH CH CH CH P N 2 INCH NPT CONNECTION TO DRAIN 1 2 INCH NPT CONNECTION FOR WATERFLOW PRESSURE ALARM SWITCH RESTRICTION ASSEMBLY SEE FIGURE 3 3 4 INCH NPT CONNECTION FOR WATER MOTOR A...

Page 14: ...7 8 225 G F E D G x G F x G C A B F x G G x G B A D E C F G With RC 1 D E F G B C Dimension A Without RC 1 Dimensions in Inches and mm 16 1 2 419 8 7 8 225 10 1 2 267 12 1 4 311 16 1 2 419 10 1 2 267...

Page 15: ...2 394 12 1 2 318 10 1 4 260 10 1 2 267 10 1 2 267 10 254 10 254 19 483 D F x G F G E D F x F D G x G C A B 11 1 2 292 11 1 4 286 11 1 2 292 12 1 4 311 2 3 4 70 15 1 2 394 12 305 12 305 12 1 4 311 11 1...

Page 16: ...38 19 1 2 495 14 356 C B A E G F G F C A B B C D E G x G F x F F x G E 3 1 2 89 15 1 2 394 16 1 2 419 16 1 8 410 18 1 2 470 3 1 2 89 N A 16 1 2 419 16 1 8 410 15 3 4 400 14 356 12 305 14 356 12 305 D...

Page 17: ...es to flow from the alarm line drain Step 6 Clean the 1 2 inch Strainer located in the valve trim as well as the 3 4 inch Strainer located at the connection to the water motor alarm as applicable Be s...

Page 18: ...lve slowly remove the plug from the supply pres sure gauge test valve to relieve the supply pressure and then slowly open the union in the externally mounted bypass Step 3 Check for leakage past the B...

Page 19: ...057 8 Inch P N 52 204 4 058 Accessories Order the following accessories as applicable Model RC 1 Retard Chamber P N 52 211 1 002 Required for variable pressure water sup ply conditions Alarm Vent Tri...

Page 20: ...N 52 203 4 715 JIS Flange x 6 62 inch 168 3 mm Groove O D P N 52 203 4 815 JIS Flange x 6 50 inch 165 1 mm Groove O D P N 52 203 5 815 6 50 inch 165 1 mm Groove O D x 6 50 inch 165 1 mm Groove O D P N...

Reviews: