background image

TFP910

Page 17 of 20

Trim kit is ordered separately when a 

Water Motor Alarm is not installed.

Care and 

Maintenance

The following procedures and 

inspections should be performed in 

accordance with this section, in addi-

tion to any specific requirements of the 

NFPA. Any impairment must be imme-

diately corrected.

NOTICE

Performing the care and maintenance 

procedures will result in operation of 

the associated alarms. Consequently, 

notification must first be given to the 

owner and fire department, central sta-

tion, or other signal station to which the 

alarms are connected.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protection 

system from the proper authorities 

and notify all personnel who may be 

affected by this decision.

The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the National Fire Protection Asso-

ciation (e.g., NFPA 25), in addition to 

the standards of any other authorities 

having jurisdiction. Contact the install-

ing contractor or product manufacturer 

regarding any questions.

Automatic sprinkler systems are rec-

ommended to be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.
The  TYCO Model AV-1-300 Alarm 

Check Valves do not require any reg-

ularly scheduled maintenance. It is 

recommended, however, that proper 

operation of the alarms be periodically 

verified in accordance with a proce-

dure that is acceptable to the authority 

having jurisdiction. Any impairment 

must be immediately corrected.

Inspection Procedure

It is recommended that the following 

inspection procedure be performed at 

least quarterly by a qualified Inspection 

Service.

Step 1.

 Notify the proper authorities 

and all personnel who may be affected 

that an alarm test is to be performed.

Step 2.

 Open the end-of-line Inspec-

tor’s Test Connection (or Alarm Test 

Valve, if acceptable to the authority 

having jurisdiction) and verify that the 

system alarms operate in accordance 

with the requirements of the authority 

having jurisdiction. Verify that the water 

motor alarm and/or the pressure alarm 

switch properly actuate and within the 

elapsed time required by the authority 

having jurisdiction.

Step 3.

 Verify that water is flowing 

out of the alarm line drain at a rate 

consistent with the 1/8 inch (3,2 mm) 

diameter drain orifice in the Restriction 

Assembly.

Step 4.

 Close the end-of-line Inspec-

tor’s Test Connection (or Alarm Test 

Valve).

Step 5.

 Verify that water ceases to flow 

from the alarm line drain.

Step 6.

 Clean the 1/2 inch Strainer 

(located in the valve trim) as well as 

the 3/4 inch Strainer (located at the 

connection to the water motor alarm, 

as applicable). Be sure to replace the 

strainer baskets and tighten the caps 

securely.

NOTICE

Cleaning of the Strainers after each 

operation of the alarms is especially 

important in the case of water sup-

plies (such as lakes and rivers) having 

a large quantity of suspended matter. A 

clogged alarm line can prevent opera-

tion of the alarms. 

Step 7.

 Notify all authorities responsi-

ble for monitoring the installation that 

the fire protection system has been 

returned to service.

Sprinkler System Drain-Down

Draining the sprinkler system must be 

done in accordance with the following 

procedure:

Step 1.

 Close the main control valve, if 

this has not already been done.

Step 2.

 Open the remote cross main or 

branch line vent connection. (Refer to 

Step 7 in the Installation section.)

Step 3.

 Open the Main Drain Valve. 

Check first to see that the drainage 

water discharge will not cause dam-

age or result in dangerous conditions.

Step 4.

 Wait until the Supply Pressure 

Gauge reads zero pressure and the 

sound of draining water has stopped 

before performing any maintenance 

work on the fire protection system.

Leakage from Alarm Line Drain

Follow the steps indicated below until 

water ceases to flow from the alarm 

line drain. After each step check if leak-

age has stopped.

Step 1.

 Open the Main Drain Valve. Let 

the water flow for about 5 seconds and 

then close the Main Drain Valve. This 

should flush any loose debris that may 

have become trapped between the 

Clapper Facing and the Seat Ring or 

in the seating area of the Drain Valve.

Step 2.

 Repeat Step 1 if the rate of 

continued flow out of the drain was 

noticeably reduced.

Step 3.

 Open the Alarm Test Valve and 

allow water to flow for about 5 seconds 

before re-closing the valve. This should 

flush any loose debris that may have 

become trapped in the seating area of 

the Alarm Test Valve.

Step 4.

 Repeat Step 3 if the rate of 

continued flow out of the drain was 

noticeably reduced.

Step 5.

 Determine whether the water is 

flowing from the Alarm Port (Ref. Figure 

1) or past the Alarm Test Valve. If the 

leakage is past the Alarm Test Valve, 

close the main control valve, and then 

repair or replace the Alarm Test Valve 

as necessary.

Step 6.

 If it appears that the leakage 

noted in Step 5 is from the Alarm Port, 

drain the system in accordance with 

the prescribed procedure. After the 

system has been drained, remove the 

Handhole Cover.

Step 7.

 While holding the Spring down 

by the coils, remove the Hinge Pin. 

Remove the Spring and Waterway 

Clapper Assembly.

1

1

QTY.

1

. . . . . . . . . . .

. . . . . . . . .

. . . . . . . . . .

1

2

NO.

3

3/32" Vent

3/4" x 1/4" Hex

Fitting

Bushing

92-032-1-002

CH

DESCRIPTION

P/N

1/4" x 5'-0"
Tubing

CH

2

(GREEN

TINT)

MODEL RC-1

RETARD

CHAMBER

PRESSURE

SWITCH

3

(ROUTE TO

DRAIN)

1

FIGURE 8 

ALARM VENT TRIM KIT 

(P/N 52-201-2-012)

Summary of Contents for AV-1-300

Page 1: ...herein must be installed and maintained in com pliance with this document as well as with the applicable standards of the National Fire Protection Association NFPA in addition to the standards of any...

Page 2: ...es 4 6 8 Inch NR Clapper See b 92 200 1 423 92 200 1 623 92 200 1 823 Hex Bolt Handhole Cover 2 1 2 Inch Valve x 1 1 4 Long CH DESCRIPTION REF VALVE PARTS 1 2 13 UNC 2A 6 Inch Valve x 1 3 4 Long CH 1...

Page 3: ...95 0 0 91 23 0 11 42 290 0 5 50 139 7 0 75 19 0 5 00 127 0 5 51 140 0 0 87 22 0 0 71 18 0 0 71 18 0 0 87 22 0 0 87 22 0 0 71 18 0 0 75 19 0 4 Inch DN100 6 Inch DN150 8 Inch DN200 2 1 2 Inch DN65 4 8 8...

Page 4: ...e TYCO Model AV 1 300 Alarm Check Valves consideration must be given to the dis posal of the large quantities of water that may be associated with draining the system or performing a flow test Valves...

Page 5: ...ch line at the point most remote from the alarm valve The vent line should be connected to the top of a cross main or to the end of a branch line and be located at the highest level of a multi level i...

Page 6: ...ple 1 4 x 2 1 2 Nipple CH DESCRIPTION 1 1 4 INCH NPT CONNECTION TO DRAIN 1 2 INCH NPT CONNECTION FOR WATERFLOW PRESSURE ALARM SWITCH RESTRICTION ASSEMBLY SEE FIGURE 3 3 4 INCH NPT CONNECTION FOR WATER...

Page 7: ...2 1 2 x 4 1 2 All Fittings and Nipples are galvanized Standard Order Install subassemblies in alphabetical order NOTES 3 1 2 CH Common Hardware 2 INCH NPT CONNECTION TO DRAIN 1 2 INCH NPT CONNECTION...

Page 8: ...ESCRIPTION CH CH CH CH CH CH P N CH 1 2 x 1 2 x 3 4 Tee All Fittings and Nipples are galvanized Standard Order Install subassemblies in alphabetical order NOTES 3 1 2 CH Common Hardware 2 INCH NPT CON...

Page 9: ...6 048 1 007 92 304 1 017 P N 1 4 90 Elbow 1 4 Plug CH CH All Fittings and Nipples are galvanized Standard Order CH Common Hardware NOTES 1 2 SUPPORT BRACKET SUPPORT BAR EXTERNAL BY PASS TUBE ALARM TES...

Page 10: ...ommon Hardware Select Appropriate Nipple Sizes per AV 1 Alarm Check Valve Size 4 Inch DN100 29 1 2 x 1 1 2 30 1 2 x 3 1 2 Nipple Number 1 2 x 2 1 2 1 2 x 4 1 2 6 Inch DN150 2 INCH NPT CONNECTION TO DR...

Page 11: ...3 4 Tee 1 2 x 1 1 2 Nipple CH All Fittings and Nipples are galvanized Standard Order Install subassemblies in alphabetical order NOTES 3 1 2 CH Common Hardware DRIP FUNNEL 2 INCH NPT CONNECTION TO DRA...

Page 12: ...TION TO DRAIN 1 2 INCH NPT CONNECTION FOR WATERFLOW PRESSURE ALARM SWITCH RESTRICTION ASSEMBLY SEE FIGURE 3 3 4 INCH NPT CONNECTION FOR WATER MOTOR ALARM 3 4 INCH NPT CONNECTION FOR WATER MOTOR ALARM...

Page 13: ...CH CH CH CH CH CH CH CH CH CH P N 2 INCH NPT CONNECTION TO DRAIN 1 2 INCH NPT CONNECTION FOR WATERFLOW PRESSURE ALARM SWITCH RESTRICTION ASSEMBLY SEE FIGURE 3 3 4 INCH NPT CONNECTION FOR WATER MOTOR A...

Page 14: ...7 8 225 G F E D G x G F x G C A B F x G G x G B A D E C F G With RC 1 D E F G B C Dimension A Without RC 1 Dimensions in Inches and mm 16 1 2 419 8 7 8 225 10 1 2 267 12 1 4 311 16 1 2 419 10 1 2 267...

Page 15: ...2 394 12 1 2 318 10 1 4 260 10 1 2 267 10 1 2 267 10 254 10 254 19 483 D F x G F G E D F x F D G x G C A B 11 1 2 292 11 1 4 286 11 1 2 292 12 1 4 311 2 3 4 70 15 1 2 394 12 305 12 305 12 1 4 311 11 1...

Page 16: ...38 19 1 2 495 14 356 C B A E G F G F C A B B C D E G x G F x F F x G E 3 1 2 89 15 1 2 394 16 1 2 419 16 1 8 410 18 1 2 470 3 1 2 89 N A 16 1 2 419 16 1 8 410 15 3 4 400 14 356 12 305 14 356 12 305 D...

Page 17: ...es to flow from the alarm line drain Step 6 Clean the 1 2 inch Strainer located in the valve trim as well as the 3 4 inch Strainer located at the connection to the water motor alarm as applicable Be s...

Page 18: ...lve slowly remove the plug from the supply pres sure gauge test valve to relieve the supply pressure and then slowly open the union in the externally mounted bypass Step 3 Check for leakage past the B...

Page 19: ...057 8 Inch P N 52 204 4 058 Accessories Order the following accessories as applicable Model RC 1 Retard Chamber P N 52 211 1 002 Required for variable pressure water sup ply conditions Alarm Vent Tri...

Page 20: ...N 52 203 4 715 JIS Flange x 6 62 inch 168 3 mm Groove O D P N 52 203 4 815 JIS Flange x 6 50 inch 165 1 mm Groove O D P N 52 203 5 815 6 50 inch 165 1 mm Groove O D x 6 50 inch 165 1 mm Groove O D P N...

Reviews: