Appendix A – AFC200 frequency converter parameters table
Parameter /
Name
Function
Available options / measurement
unit / comments
Factory
setting
Change
during
opera-
tion
2.90
K1 funct. 1
Function 1 of the
K1 relay
0-Not active:
relay inactive
1-Operation:
active when there is
voltage supplied to motor
2-Ready:
the device is ready for work
3-Fail.:
a failure has occurred
4-n.Flr.:
no failure
5:
not used
6:
not used
7-Fthr1:
F threshold 1 exceeded
8-Fthr2:
F threshold 2 exceeded
9-F.ref.:
referenced frequency
reached
10-Thrs.T:
warning of exceeding pro-
grammed
threshold of heatsink tem-
perature
11-Warn.A: warning: error of ana-
log signal (lack of
“living null” signal
lower than 2V or 4mA);
(the system has a dead band in the
range of 2..1V and 4..2mA - a warning
will appear only after exceeding it)
12-Act.DI1:
digital input DI1 is active
13-Act.DI1-2:
digital input
DI1 or DI2
is active
14-Act.DI1-3:
digital input
DI1, DI2 or
DI3
is active
2
YES
2.91
K1 funct. 2
Function 2 of K1
relay
As above
0
YES
2.92
K2 funct. 1
Function 1 of K2
relay
As above
0
YES
2.92
K2 funct. 2
Function 2 of K2
relay
As above
0
YES
2.98
F thresh. 1
Threshold fre-
quency 1
0.00 ... 320.0 Hz
25.00 Hz
YES
2.99
F thresh. 2
Threshold fre-
quency 2
0.00 ... 320.0 Hz
45.00 Hz
YES
2.100
Temp.Warn.
Threshold of
controller
overheat warn-
ing
0 ... 80 °C
70 °C
YES
2.110
Operat. Perm.
External opera-
tion permission
0-Off:
operation is not allowed
1-DI1 .. 6-DI6:
operation is allowed,
when there is a voltage supplied on
digital input DI1...DI6
7-On.:
operation is allowed
7
YES
66