Section 8: Failures and warnings
Code
Display view
Description
Possible cause
Counteraction
E. 4
Low voltage in DC
circuit
Low voltage in circuit,
absence of one sup-
ply phase.
Check wires and
supply voltage level.
E. 5
Short circuit at the
system output or
power module fault.
Short circuit in elec-
tric motor or motor
power cable.
Disconnect the mo-
tor and check if the
fault persists; if it is
present, contact the
service centre, if not
—check insulation of
motor wires and
windings.
E. 6
Electric motor cur-
rent is too high.
Too intensive start-
up.
A rapid change in
motor load.
Increase motor ac-
celeration time in
par. 1.30.
E. 7
Electric motor
thermal overload.
Operation with a
loaded motor or long
operation with high
loading at low
speeds
Check motor load
(motor current).
Check the paramet-
ers of the motor
thermal model
U. 8
No signal at the
analog input.
When setting the in-
put with "living null"
(2-10V or 4-20mA -
par. 2.40) the signal
is below 1V or 2mA.
Depending on the
setting of par. 3.23,
the warning (U.8) or
failure (E.8) occurs.
Check the configura-
tion of the analog in-
puts, check the con-
nection system
(broken wires etc.)
E. 8
E. 13
Heatsink temperat-
ure is lower than
-10ºC.
The ambient temper-
ature of the freqency-
converter is too low.
Check heating effi-
ciency.
E. 21
The signal of ex-
ternal failure is act-
ive
Depending on the
User's configuration,
Check the status at
the digital input se-
lected as an external
fault.
E. 27
Waiting time for RS
signal is exceeded.
Cable damage, para-
meters of the trans-
mission are incor-
rectly set up.
Check external con-
nection and correct-
ness of RS paramet-
ers.
8.2.
Deleting failure message.
Manual deleting
To delete the failure message press the stop button (
) for at least 2
seconds.
52
TWERD Power Electronics
REF
Hz
rpm
RUN
REV
FAULT
REF
Hz
rpm
RUN
REV
FAULT
REF
Hz
rpm
RUN
REV
FAULT
REF
Hz
rpm
RUN
REV
FAULT
REF
Hz
rpm
RUN
REV
FAULT
REF
Hz
rpm
RUN
REV
FAULT
REF
Hz
rpm
RUN
REV
FAULT
FAULT
REF
Hz
rpm
RUN
REV
REF
Hz
rpm
RUN
REV
FAULT