Appendix A – AFC200 frequency converter parameters table
Parameter /
Name
Function
Available options / measurement
unit / comments
Factory
setting
Change
during
opera-
tion
2.46
AI1 Offs.
Offset of analog
referencing-
unit
RefA1
-500.0 ... 500.0 %
0.0 %
YES
2.47
AI2 Offs.
Offset of analog
referencing-
unit
RefA2
-500.0 ... 500.0 %
0.0 %
YES
2.49
Filter AI1
Low-pass filter
time constant
0.00 ... 50.00 s
0.10 s
YES
2.50
Filtr AI2
Low-pass filter
time constant
0.00 ... 50.00 s
0.10s
YES
2.60
PI Ref.Src
Choice of PI
controller
referencing-unit
0-Keyb..:
referencing frequency from
panel
1-AI1:
referencing frequency by signal
from analog
input AI1
2-AI2:
referencing frequency by signal
from analog input AI2
3:
not used
4-RS:
referencing through RS-485
link
0
YES
2.61
PI Inp.Src
Choice of
regulated value
of PI controller
0-Ref.A1:
referencing regulated value
from analog referencing-unit
Ref.A1
1-Ref.A2:
referencing regulated
value from analog referencing-unit
Ref.A1
0
YES
2.62
Negation of
error
Negation of con-
troller error
0:
NO
1:
YES
0
YES
2.63
P Amp.
Amplification of
proportional
element of
PI controller
0 ... 3000 %
100 %
YES
2.64
I constant
Time constant of
PI controller
0.00 ... 320.0 s
0.10 s
YES
2.66
max.Out. PI
Upper limitation
of PI controller
output value
0,0 ... 300,0 %
100.0 %
YES
2.67
min.Out. PI
Lower limitation
of PI
controller output
value
-300,0 ... 0,0 %
0.0 %
YES
64