Appendix A – AFC200 frequency converter parameters table
Parameter /
Name
Function
Available options / measurement
unit / comments
Factory
setting
Change
during
opera-
tion
1.20
Operating
mode
Frequency con-
verter operating
mode
0-U/f lin.:
operation in scalar mode
(linear characteristic)
1-U/f sq.:
as above (square-law char-
acteristic)
2:
not used
3-Vector:
operation in vector mode
0
NO
1.21
F carrier
Switching fre-
quency
0:
4kHz
1:
8kHz
2:
16kHz
0
NO
1.30
Acceleration
Acceleration
time from 0 Hz to
50 Hz
0.0 ... 320.0 s
5.0 s
YES
1.31
Deceleration
Deceleration
time from 50Hz
to 0Hz
0.0 ... 320.0 s
5.0 s
YES
1.37
Initiation time
Time after which
it will be possible
to start the fre-
quency con-
verter from the
moment of sup-
plying power
0...200s
0 s
YES
1.38
Stop delay
The start time of
stopping when
the STOP signal
has been given
0...200s
0 s
YES
1.40
F max
Maximum output
frequency
0.0 ... 320.0 Hz
Note: See also par. 2.12
55.0 Hz
YES
1.41
I limit S
Current restric-
tion at electric
motor operation
0.0 ... 200.0 % motor In
150.0 %
YES
1.43
M limit S
Torque restric-
tion at motor op-
eration
0.0...200.0% motor Mn
150.0%
YES
1.50
U0
Voltage for out-
put frequency F0
(par. 1.51)
0.0 ... 40.0 % motor Un
2.0 %
YES
1.51
F0
F0 frequency
0.0 ... 20.0 %
0.0 %
YES
1.52
U1
Voltage for out-
put frequency F1
(par 1.53)
0.0 ... 40.0 %
20.0 %
YES