ACM 400 S motor control unit
21 / 24
8
00...18
Function of the PHOTOELECTRIC BARRIER
Opening
Closing
00
No effect
No effect (test purposes)
01
No effect
Stop
02
No effect
Release
03
No effect
Reversing
04
Stop
No effect
05
Stop
Stop
06
Stop
Release
07
Stop
Reversing
08
Release
No effect
09
Release
Stop
10
Release
Release
11
Release
Reversing
12
Reversing
No effect
13
Reversing
Stop
14
Reversing
Release
15
Reversing
Reversing
16
No effect
Reversing
Closure 0.5s after LS
warning time 0,5s
17
No effect
Reversing
Closure 3.0s after LS
warning time 1.5s
18
No effect
Reversing
Closure 7.0s after LS
warning time 4.0s
05
9
00 / 01
EMERGENCY STOP
00
keep open time (automatic closing) starts again from beginning after
Emergency stop.
01
After Emergency stop Automatic closing is blocked until next command.
01
(Block AZ)
A
00...60
UNIVERSAL INPUT function:
00
Time switch: Automatic closing only when closed contact
01...60
Partial opening function with 1...60s partial opening time
05
(5s partial
opening)
B
00...15
RELEASE TIME
Release after photoelectric barriers or safety strips command
00...15
0.25s...4,00s in 0.25s steps
07
(2.00s)
C
00...03
RADIO OPEN / CLOSED while motor running
00
FUNK-OPEN: Stop during opening, Stop while closing (panic function)
RADIO CLOSED: Stop while opening, Stop while closing (panic function)
01
RADIO OPEN: No effect while opening, Reversing while closing
RADIO CLOSED: Stop while opening, Stop while closing (panic function)
02
RADIO OPEN: Stop while opening, Stop while closing (panic function)
RADIO CLOSED: Reversing while opening, no effect while closing
03
RADIO OPEN: No effect while opening, Reversing while closing
RADIO CLOSED: Reversing while opening, no effect while closing
00
(Panic function)
D
00...03
inputs OPEN / CLOSED while motor running
00
OPEN: Stop while opening, Stop while closing (panic function)
CLOSED: Stop while opening, Stop while closing (panic function)
01
OPEN: No effect while opening, Reversing while closing
CLOSED: Stop while opening, Stop while closing (panic function)
02
OPEN: Stop while opening, Stop while closing (panic function)
CLOSED: Reversing while opening, no effect while closing
03
OPEN: No effect while opening, Reversing while closing
CLOSED: Reversing while opening, no effect while closing
00
(Panic function)
E
00...03
PULSE / DEAD MAN’s mode with OPEN / CLOSED input
00
OPEN: Pulse CLOSED: Pulse
01
OPEN: Pulse CLOSED: dead man’s
02
OPEN: dead man’s CLOSED: Pulse
03
OPEN: dead man’s CLOSED: dead man’s
00
(Pulse)
F
00…02
UNIVERSAL OUTPUT 2
00
Photoelectric barrier test (interruption in transmitter voltage)
01
T
raffic signal lights (idle position in limit position “Open“, otherwise always
connected)
02
Radio button (channel 4)
01
(Traffic signal
light)
H
Display only!
READ OUT TRIPS COUNTER
Left position: “0“...“5“, right position corresponds to 100,000s... 1s
-
L
00 / 01
SERVICE MODE
00
Control panel unblocked, normal setting possibilities
01
Control panel locked, no changes possible.
Change from Menu “F“:
Emergency stop, Key + and Key - actuated,
Switch over with menu key!
00
(unblocked/releas
ed)