V02.00 | 2021/11
17
5
Installing
5.1
Installing the device in Zone 2 and Zone 22
In Zone 2 and Zone 22, the devices can be used in conjunction with the protective housing set .
DANGER
Potentially explosive atmosphere
Risk of explosion through spark ignition
For use in Zone 2 and Zone 22:
Only install the device if there is no potentially explosive atmosphere present.
Observe requirements for Ex approval.
Unscrew the housing. Use Torx T8 screwdriver.
Replace the service window with the enclosed Ultem window.
Place the device on the base plate of the protective housing and fasten both together on
the mounting plate, see [
21].
Mount and screw the housing cover according to the following figure. The tightening
torque for the Torx T8 screw is 0.5 Nm.
Fig. 3: Mounting the device in protection housing TB-SG-L