background image

 

E14 

Indicates that a valve in short circuit has 

been excluded from the cycle. 

The signaling of the code E14 alternates 

with the indication of the interested 

output is shown as Uxx where xx is the 

number of the output. 

An output is considered a short circuit if 

not responding for 3 following 

activations. 

An activation without error resets the 

counting. 

Switch the device off and back on after 

having checked the solenoid valve 

system. 

Description Of Operation  

The installed SW version and the symbol 

---

, meaning that coherence between settings 

stored in E2Prom and the set jumpers is being checked, will appear on the display when 
the sequencer is powered up. A corresponding error code will appear in case of 
discrepancies between settings (see Alarms Table). Only editing functions will be allowed 
on the unit. The operator may switch off the unit and configure the jumpers correctly. 
Symbol 0_0 will appear on the display if the test is entirely successful.  
The following pages will then appear: 

 

OFF if the enabling contact is open (14-15) 

 

-0- if the enabling contact (14-15) is closed and the fan is off  

Operative Mode  

The  device  works  as  a  programmable  cycle  sequencer.  The  connected  outputs  will  be 
activated at the programmable frequencies. The firing and pausing times can be set on the 
configuration menu. 

Cleaning Function With Fan Off (PCC) 

This  function  allows  to  carry  out  one  or  more  cleaning  cycles  (the  number  of  cycles  is 
defined by F13) when the fan is off. The on or off state of the fan is determined by the 
state of contacts 12-13 (contacts open = fan off). The pulse time of the valves will always 
be that defined in F02, while the pause time in this case is defined in F14. 
The display alternately shows the number of the valve activated and the word PCC. 

Number Of Output Selection

 

The number of outputs (solenoid valves) on which the sequencer will run the cleaning cycle 
can  be  selected.  Cleaning  will  be  carried  out  in  order  from  the  first  to  the  last  solenoid 
valve. The valves can be adjusted by the F04 function. 

Fuse

 

A fuse which can be reset in case of need is located near the power terminal board. Use a 
delayed fuse 5x20mm. 
 
 
 
 
 
 

Summary of Contents for E1T 16

Page 1: ...T USER MANUAL 01 03 2016 Manual Release 1 24 Hardware Release 1 3 TURBO s r l Electronic Control Systems for Dust Collectors e mail info turbocontrols it web www turbocontrols eu TEL 39 0 362 574024 F...

Page 2: ...e IK07 2 Joule EN62262 Performance Of The Device LED display with 7 segments 3 digits 0 8 each Operating times expressed in seconds with selectable ranges for any application Power supplier 115 230 Va...

Page 3: ...ally closed The activation of a solenoid valves causes them to open and consequently let out a jet of air Alarm Relays The alarm relays has two voltage free contacts on terminals 4 5 Relay 1 and 6 7 r...

Page 4: ...oned in a place easily accessible Before working on the equipment to perform any operation switch off the magneto thermic differential switch For electric operations always remove voltage wait 30 seco...

Page 5: ...correct use of the device may cause damage to the device or to the devices connected to it Furthermore incorrect use or tampering with the device may cause injury Waterproofness of the casing is guara...

Page 6: ...o select and then and increase or decrease the values The OK button is used to confirm data and reset alarms If the button is pressed during ordinary operation the activity hour meter is displayed The...

Page 7: ...ping the fan Possible values 01 99 step 1 Default 01 F14 Post cleaning mode pause time fan off Possible values 001 999 step 1 Default 010 F15 Maintenance frequency expressed in tens of hours e g 1 10h...

Page 8: ...detected To use 115V valves switch the device off and move the output voltage selection jumper to 115V If the jumper is in the correct position press OK then SET select the F05 function with and set 1...

Page 9: ...ing pages will then appear OFF if the enabling contact is open 14 15 0 if the enabling contact 14 15 is closed and the fan is off Operative Mode The device works as a programmable cycle sequencer The...

Page 10: ...9 Connection Diagram...

Page 11: ...Maintenance interval has been reached If one of these occurs the relay is activated Terminal Table Terminal n Description Terminal n Description 1 Power supply 115 230 Vac 32 Solenoid 2 output 2 Powe...

Page 12: ...11 Jumper Configuration Power Input 115 230 VAC 115 VAC 230 VAC Jumper Configuration Output 115 VAC 230 VAC 24 VAC 24 VDC...

Page 13: ...12 Installation Casing Dimensions 4 8 Outputs Weight 1 8 Kg...

Page 14: ...13 Installation Casing Dimensions 12 16 Outputs Weight 2 1 Kg...

Page 15: ...of cycles after fan stop 1 F14 Pause time between solenoid valves in cycle with fan off 010 F15 Maintenance frequency in 10h 1 10h 100 1000h 100 F16 Maintenance deadline alarm on 1 or off 0 0 F17 Main...

Page 16: ...d vale output voltage agree Check wiring between sequencer and solenoid valves Do alarm messages appear Check the alarm code with the table Do the alarms fail to activate signalling devices System wir...

Page 17: ...Product Options All Complies with the following directives Electromagnetic Compatibility Directive 2014 30 EU meeting EU harmonised standards EN61000 6 2 2005 class B of Standard EN61000 6 4 2001 Low...

Reviews: