2
Important: Read the installation
instruction section before
connecting the device.
Electric Specifications
Electric Power:
•
115 Vac ± 10% 50-60 Hz – 25W
•
230 Vac ± 10% 50-60 Hz – 25W
•
24 Vac ± 10% 50-60 Hz – 25W (Optional)
•
24 Vdc ± 10% 25W (Optional)
Selectable Output Voltage:
•
24 Vdc
•
24 Vac
•
115 Vac
•
230 Vac
Inputs And Outputs Not Galvanically Insulated:
•
Enable contact (remote cleaning enable).
•
Fan contact (post-cleaning).
The solenoid valves connected to the unit are normally closed.
The activation of a solenoid valves causes them to open and consequently let out a jet of
air.
Alarm Relays:
The alarm relays has two voltage-free contacts on terminals 4-5 (Relay 1) and 6-7 (relay 2).
Maximum permitted load: 3A @ 250Vac - 2A @ 24Vdc, 24 Vac.
The relays are normally closed, opens in case of alarms, and opens with the control unit
off or in the absence of power.
Fuse
1 x 1 A @ 230 Vac 1 x 1 A @ 115 Vac.
1 x 3 A @ 24 Vac 1 x 3 A @ 24 Vdc.
Working Temperature:
from -10°C to 55°C
Storage Temperature:
from -20°C to 60°C
Timer Specifications:
Pulse Time (Valve Opening)
from 50 msec. to 5 sec.
Pause Time (Interval Between Valve Openings)
1 sec - 999 sec.