background image

 

 

 

The cable glands must be chosen according to the diameter of the cable to be used. 

 

The sealing of the press cable is guaranteed by the compression of the rubber gasket 
that tightens on the outer diameter of the cable. 

 

The tightness of the cable gland is guaranteed by the compression of the rubber seal 
that tightens on the outer diameter of the cable. 

 

The size of cable and cable gland must ensure that a power cord traction is not 
acting on the terminals. 

 

The terminal block must not be the point of mechanical anchoring of the conductors. 

 

The cable gland PG9 supplied on request, has cable diameter minimum of 4mm and a 
maximum of 8mm, with clamping nut by 19mm. 

 

Any use not described in this user instruction manual or incorrect use of the device 
may cause damage to the device or to the devices connected to it. 

 

Furthermore, incorrect use or tampering with the device may cause injury. 

 

Waterproofness of the casing is guaranteed when the flap is closed. 

 

Make sure that rigid or flexible ducts used for wiring, if any, do not fill up with water 
or other liquids. 

 

Do not make holes not protected on the container or protected by accessories with 
protection degree lower than that of the housing of the control unit. 

 

Cut off power supply immediately if water is found in the casing. 

 

If the control unit is used in ways not specified by the manufacturer, the protection 
provided by the device may be impaired. 

 

The Control Unit does not release potentially toxic or harmful substances to the 
health and the environment. 

 

No part with dangerous voltage is normally accessible. 

 

Do not use the control unit if you have not read or do not understand this manual. 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for E1T 16

Page 1: ...T USER MANUAL 01 03 2016 Manual Release 1 24 Hardware Release 1 3 TURBO s r l Electronic Control Systems for Dust Collectors e mail info turbocontrols it web www turbocontrols eu TEL 39 0 362 574024 F...

Page 2: ...e IK07 2 Joule EN62262 Performance Of The Device LED display with 7 segments 3 digits 0 8 each Operating times expressed in seconds with selectable ranges for any application Power supplier 115 230 Va...

Page 3: ...ally closed The activation of a solenoid valves causes them to open and consequently let out a jet of air Alarm Relays The alarm relays has two voltage free contacts on terminals 4 5 Relay 1 and 6 7 r...

Page 4: ...oned in a place easily accessible Before working on the equipment to perform any operation switch off the magneto thermic differential switch For electric operations always remove voltage wait 30 seco...

Page 5: ...correct use of the device may cause damage to the device or to the devices connected to it Furthermore incorrect use or tampering with the device may cause injury Waterproofness of the casing is guara...

Page 6: ...o select and then and increase or decrease the values The OK button is used to confirm data and reset alarms If the button is pressed during ordinary operation the activity hour meter is displayed The...

Page 7: ...ping the fan Possible values 01 99 step 1 Default 01 F14 Post cleaning mode pause time fan off Possible values 001 999 step 1 Default 010 F15 Maintenance frequency expressed in tens of hours e g 1 10h...

Page 8: ...detected To use 115V valves switch the device off and move the output voltage selection jumper to 115V If the jumper is in the correct position press OK then SET select the F05 function with and set 1...

Page 9: ...ing pages will then appear OFF if the enabling contact is open 14 15 0 if the enabling contact 14 15 is closed and the fan is off Operative Mode The device works as a programmable cycle sequencer The...

Page 10: ...9 Connection Diagram...

Page 11: ...Maintenance interval has been reached If one of these occurs the relay is activated Terminal Table Terminal n Description Terminal n Description 1 Power supply 115 230 Vac 32 Solenoid 2 output 2 Powe...

Page 12: ...11 Jumper Configuration Power Input 115 230 VAC 115 VAC 230 VAC Jumper Configuration Output 115 VAC 230 VAC 24 VAC 24 VDC...

Page 13: ...12 Installation Casing Dimensions 4 8 Outputs Weight 1 8 Kg...

Page 14: ...13 Installation Casing Dimensions 12 16 Outputs Weight 2 1 Kg...

Page 15: ...of cycles after fan stop 1 F14 Pause time between solenoid valves in cycle with fan off 010 F15 Maintenance frequency in 10h 1 10h 100 1000h 100 F16 Maintenance deadline alarm on 1 or off 0 0 F17 Main...

Page 16: ...d vale output voltage agree Check wiring between sequencer and solenoid valves Do alarm messages appear Check the alarm code with the table Do the alarms fail to activate signalling devices System wir...

Page 17: ...Product Options All Complies with the following directives Electromagnetic Compatibility Directive 2014 30 EU meeting EU harmonised standards EN61000 6 2 2005 class B of Standard EN61000 6 4 2001 Low...

Reviews: