The ATS Series is designed to be mounted in a rack, on a horizontal surface
such as a desk, or a floor or wall using the optional MK-5000C brackets with
hardware.
- The ATS must be protected by an upstream branch circuit protector, for
both the Primary and the Backup, at 125% of the ATS current rating (the
maximum input current rating as shown on the ATS product label) per the
National Electric Code or per local electrical codes if outside of the United
States.
•
Note the following if an ATS without internal circuit breakers is being
installed;
- For permanently connected equipment, a readily accessible disconnect
device shall be incorporated external to the equipment.
- For pluggable equipment, the socket-outlet shall be installed near the
equipment and shall be easily accessible.
CAUTION: THE UNIT MUST BE PLACED IN A WELL - VENTILATED AREA TO
PREVENT RISK OF FIRE DUE TO OVERHEATING. VENTILATION SLOTS MUST
NOT BE OBSTRUCTED.
•
Select an area with enough space to provide sufficient clearance around
the unit to provide unrestricted access.
3.2 REQUIRED TOOLS
•
Set of standard hand tools
•
Wire stripper (for hardwired units)
3.3
UNPACKING & INSPECTION
3.31 The units are shipped in individual cartons and may come stacked on wooden
pallets depending on the size of the order. In this configuration, the units are
placed on the pallet, with protective material between them.
3.32 Carefully open the cartons, making sure not to damage the units, and remove the
protective wrap and packing material.
3.33 Before the units are removed from the cartons, inspect them for physical damage.
3.34 If no damage is found, remove the units from the carton, open the top cover and
again inspect for damage. If damage is found in either steps 3.33 or 3.34, do not
accept the shipment and file a claim with the carrier. Contact TSi Power for
assistance if necessary.