The use of gas tanks from which gas is
extracted in the gas
phase
is mandatory when operating the MonoControl CS
gas pressure regulation system. Gas tanks from which gas is
taken in the liquid phase (e.g. for fork lifts) must not be used,
since they would result in damage to the gas system.
Start-up
Open gas remote switch if present.
1. Open extraction valve.
2. If necessary (e.g. after a new installation), press the green
reset button (crash sensor triggering element reset) at the
MonoControl CS gas tank.
1.
2.
Checking for leaks in the high pressure area
The screw joints must be tested for leaks using suitable
means (such as a leak finder spray in accordance with
EN 14291).
This is the responsibility of the operator.
Checking for leaks in the low pressure area
(maximum test pressure 150 mbar)
Test must be conducted by a technician!
Turn off all consumers.
Open stop valves and, if present, gas remote switch.
Remove the threaded cap from the test connection (b)
and connect the test pump with test hose to the test
connection.
b
Conduct leak test (in Germany according to G 607, for
example).
If gas system exhibits a leak, close the extraction valve and
have the gas system repaired immediately by an expert; do
not open the extraction valve until repair is complete.
When testing is complete, screw the threaded cap back
onto the test connection.
–
–
–
–
–
–