Fig. 8: Cross bars
1.
Remove the cross bars ( Fig. 8 /1) that are
marked with a red sticker ( Fig. 8 /2).
Note: Do not remove any of the painted cross
bars that do not carry a sticker!
2.
Then close the drilled holes in the frame with
Transport protection device for the fan (only with X-
CUBE)
The
X-CUBE Compact
only has EC fans installed in it
which do not have any transport protection brackets
because they are screwed to the casing wall.
Fig. 9: Transport protection brackets
1.
Remove the brackets ( Fig. 9 /1) that are marked
with a red sticker ( Fig. 9 /2).
2.
Then close the drilled holes in the floor of the AHU
casing with screws and washers.
Transport protection device Vibration Baseframe
Air handling units with Vibration Baseframe have special
transport protection devices between the base frame
and the unit. These must be removed before commis-
sioning, as otherwise the sound insulation will not work.
Fig. 10: Transport protection device on units with Vibra-
tion Baseframe
1.
Unscrew screws on the transport protection
devices ( Fig. 10 /1) using tool (TX30) and remove
the metal sheets.
2.
Then screw the screws back into the unit.
Transport and storage
Unpacking > Removing transport protection devices
Air handling unit X-CUBE X2 / X-CUBE X2 compact
20