20
5
ELECTRICAL SAFETY
GROUNDING
This product must be grounded. If it should malfunction or breakdown, grounding provides a path of least
resistance for electric current to reduce the risk of electrical shock. This system is equipped with a cord hav-
ing an equipment-grounding conductor and a grounding plug. The plug must be plugged into an appropriate
outlet that is properly installed and grounded in accordance with all local codes and ordinances.
DANGER – Improper connection of the equipment-grounding conductor can result in a risk of electrocution.
Check with a qualified electrician or service personnel if you are in doubt as to whether the outlet is properly
grounded. Do not modify the plug provided with this system – if it will not fit the outlet, have a proper outlet
installed by a qualified electrician. Do not use any type of adapter with this system.
GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
To comply with the National Electrical Code (NFPA 70) and to provide additional protection from the risk of
electric shock, this system should only be connected to a properly grounded, grounding-type power supply
receptacle that is protected by a Ground Fault Circuit Interrupter (GFCI). Inspect operation of GFCI as per
manufacturers suggested maintenance schedule.
EXTENSION CORDS
If an extension cord is necessary, use only 3-wire extension cords that have 3-prong grounding-type plugs and
3-pole cord connectors that accept the plug from this system. Use only extension cords that are intended for
outdoor use. Use only extension cords having an electrical rating not less than the rating of the system. A
cord rated for less amperes or watts than this system rating may overheat. Exercise caution when arranging
the cord so that it will not be tripped over or pulled. Do not use damaged extension cords. Examine extension
cord before using and replace if damaged. Do not abuse extension cord. Keep extension cord away from heat
and sharp edges. Always disconnect the extension cord from the receptacle before disconnecting this system
from the extension cord. Never yank cord to pull plug from outlet. Always grasp the plug and pull to
disconnect.
Troubleshooting
TrojanUVMax Troubleshooting for all Models
SITUATION
POSSIBLE CAUSE
POSSIBLE SOLUTION
Indicator light does NOT glow
and alarm does NOT sound
Unit is unplugged
No power at AC power outlet
Power cord is damaged
Power surge caused damage to
electrical assembly
Plug unit into AC power outlet
Replace fuse or reset breaker
Replace power cord
Replace power supply
Breaker repeatedly trips
Lamp harness is wet
Clean and dry the lamp harness, check
unit for leaks
Short circuit in the electrical
assembly
Replace power supply
Leak at inlet or outlet
Threaded pipe fittings are leaking
Clean threads, reseal with Teflon tape,
and re-tighten
Adapter kit not tight
Check sealing rings and washers
Leak detected from area of
reactor
Condensation of moist air on cold
reactor (slow accumulation)
Control humidity, relocate unit, or insulate
reactor
O-ring at sleeve bolt damaged,
deteriorated, or incorrectly installed
Inspect and replace if defective
Sleeve bolt not properly installed
(too tight or not tight enough)
Tighten sleeve nut (finger tight) then
tighten1/5 turn more
O-ring at UV sensor is damaged,
deteriorated, or incorrectly installed
Inspect and replace if defective
Indicator light glows GREEN and
alarm is sounding
Electronic circuit board failure
Replace power supply
Elapsed Time Meter changes to
indicate
L0
,
L1
,
L2
, or
L3
If Elapsed Time Meter indicates 12,
lamp should be changed
Check power supply by trying a new lamp.
Replace lamp. Reset Elapsed TIme Meter.
Indicator light glows RED and
alarm sounds
Lamp is not operating
Check for continuity across lamp pins,
replace lamp if reading is open
Indicator light is flashing RED
Alarm postpone button has been
pressed
Check for lamp continuity or if the Elapsed
Time Meter reading is 12 or more
Indicator light does not glow and
alarm is sounding
Lamp not operating due to burnout
or damage to electrical pins
Check for continuity across lamp pins,
replace lamp if reading is open.