The output signal of all OUT ports is 24V, and a relay with a rate
DC above 24V must be connected externally
1) Enter the output port test interface, select all output ports to turn
off
2) Connect an output port, press the corresponding output port
button on the test interface to test whether the output port is normal,
3) If it is not normal,
One: remove the terminal, measure the OUT port with a
multimeter, when the corresponding OUT port is found in the test
interface, the normal situation (choose "ON" output voltage is 24V,
select "OFF" output voltage is 0V,); other ca
this OUT port broken
Two: Check whether the wiring of the relay is correct. Be sure to
check the wiring of the relay electrical symbol. The output port must
be connected to the positive pole of the relay.
Three: In the case of wiring pa
port of the test interface, if a tick can be received, the relay indicator
lights up basically the relay is good; if there is no sound, this relay is
a bad relay
4) If the test is normal, continue to connect to the next o
and repeat the above actions. Until the required OUT port is
connected.
5) Finally, click the "ON" or "OFF" button of the output port on the
output port test interface. One
OUT ports are normal
4: Set the reset direction and key direction of all axes
Motion controller user manual
The output signal of all OUT ports is 24V, and a relay with a rate
DC above 24V must be connected externally
1) Enter the output port test interface, select all output ports to turn
2) Connect an output port, press the corresponding output port
button on the test interface to test whether the output port is normal,
3) If it is not normal,
One: remove the terminal, measure the OUT port with a
multimeter, when the corresponding OUT port is found in the test
interface, the normal situation (choose "ON" output voltage is 24V,
select "OFF" output voltage is 0V,); other cases are regarded as
this OUT port broken
Two: Check whether the wiring of the relay is correct. Be sure to
check the wiring of the relay electrical symbol. The output port must
be connected to the positive pole of the relay.
Three: In the case of wiring pair, press the corresponding output
port of the test interface, if a tick can be received, the relay indicator
lights up basically the relay is good; if there is no sound, this relay is
4) If the test is normal, continue to connect to the next o
and repeat the above actions. Until the required OUT port is
5) Finally, click the "ON" or "OFF" button of the output port on the
output port test interface. One-click to check whether the required
OUT ports are normal
reset direction and key direction of all axes
TC-6832
Motion controller user manual
37
The output signal of all OUT ports is 24V, and a relay with a rated
1) Enter the output port test interface, select all output ports to turn
2) Connect an output port, press the corresponding output port
button on the test interface to test whether the output port is normal,
One: remove the terminal, measure the OUT port with a
multimeter, when the corresponding OUT port is found in the test
interface, the normal situation (choose "ON" output voltage is 24V,
ses are regarded as
Two: Check whether the wiring of the relay is correct. Be sure to
check the wiring of the relay electrical symbol. The output port must
ir, press the corresponding output
port of the test interface, if a tick can be received, the relay indicator
lights up basically the relay is good; if there is no sound, this relay is
4) If the test is normal, continue to connect to the next output port
and repeat the above actions. Until the required OUT port is
5) Finally, click the "ON" or "OFF" button of the output port on the
click to check whether the required