Very Important Installation Guidance
DO NOT
install the Triton Xerophyte Mixer Unit where it can become frozen.
DO NOT
install the Triton Xerophyte Mixer Unit where it can be subjected to
ambient temperatures above 40
°
C.
DO NOT
position the Triton Xerophyte Mixer Unit where maintenance access is poor or
unsafe.
DO NOT
install into a system where the cold water cistern holds less than 115 litres (230
litres if other outlets use the same cistern).
DO NOT
install into a system where air locking could occur.
DO NOT
install the wireless Triton Xerophyte Controller Unit in a position where
communication with the Triton Xerophyte Mixer Unit is poor e.g installed under a metal bath,
in front of a metal cistern, on foil backed plasterboard, outside of the 10-metre range.
DO NOT
install the Triton Xerophyte Mixer Unit onto shared water supplies.
DO NOT
fit plastic pipework unless rigidly supported.
DO NOT
install the Triton Xerophyte Mixer Unit less than 100mm from the lowest level of
water in the cistern.
Triton Xerophyte
Mixer Installation
2 1
Switch MUST be easily accessible
Installation Schematic
Mixer Unit
Controller Unit
Shower Fitting
Mixer Unit to be
within 10 metre
range