Water requirements

B-007-A

WATER REQUIREMENTS

The installation must be in accordance with 
Water Regulations/Bylaws.
To ensure activation of the heating elements, the 
shower must be connected to a mains water 
supply with a minimum running pressure of 
100kPa (1.0 bar) at a minimum flow rate of eight 
litres per minute for the 8.5kW rated model and 
nine litres per minute for the 9.5kW rated model.
For all units the maximum static pressure must 
be no greater than 1000kPa (10 bar).
If in any doubt, the pressure should be checked. 

Note:

 If the stated flow rates are not available, it 

may not be possible to achieve optimum 
performance from the unit throughout the year.
During periods of high ambient temperatures it 
may be necessary to select a low power setting 
to achieve your preferred shower temperature.
The water supply can be taken from a cold water 
storage cistern provided there is a minimum 
head of ten metres. Minimum head is the vertical 
distance from the base of the cistern to the 
showerhead. It must be an independent supply 
to the shower only.
If it is intended to operate the shower at 
pressures above the maximum or below the 
minimum stated, contact Triton Customer 
Service for advice.

Fig.  

 shows a typical system layout.

Do not use jointing compounds on any pipe 
fittings for the installation.

5

Summary of Contents for Excite Eco

Page 1: ...s Excite Eco electric shower 2180695E April 2018 Installers please note these instructions are to be left with the user ECO STATEMENT This product has been designed to deliver an average flow of below...

Page 2: ...ts diagram 21 Guarantee service policy etc rear cover CONTENTS Page To check the product suitability for commercial and multiple installations please contact Triton s specification advisory service be...

Page 3: ...nd could also cause the PRD Pressure Relief Device in the unit to operate 1 9 This product is not suitable for mounting into steam rooms or steam cubicles 2 PLUMBING 2 1 The plumbing installation must...

Page 4: ...ter becomes too hot and you cannot obtain cooler water first check that the sprayplate in the showerhead has not become blocked DO NOT place items such as soap or shampoo bottles on top of the unit Li...

Page 5: ...ry area 6 Wall screw fixing 7 Terminal block 8 Power selector 9 Stabilising valve 10 Solenoid valve 11 Guide pockets 12 Can and element assembly 13 Thermal cut out main 14 Earth connection 15 Pressure...

Page 6: ...bt switch off the whole installation at the mains supply and remove the correct fuse 3 The shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a ring main sp...

Page 7: ...ng in a bath or shower cubicle It should be readily accessible to switch off after using the shower 7 Where shower cubicles are located in any rooms other than bathrooms all socket outlets in those ro...

Page 8: ...tic pressure must be no greater than 1000kPa 10 bar If in any doubt the pressure should be checked Note If the stated flow rates are not available it may not be possible to achieve optimum performance...

Page 9: ...wall always mount the unit on the surface of the tiles NEVER tile up to the unit Refer to fig 6 for the correct siting of the shower Position the unit where it will NOT be in direct contact with water...

Page 10: ...ce cable entry from the top is required then a small area will need to be cut out in the backplate fig 9 If installing a feed pipe from the rear bottom or side the centre of the inlet valve to the wal...

Page 11: ...the wall Hook the backplate over the top and bottom screws and fit the centre fixing screw into position Do not fully tighten the screws at this stage as the fixing holes are elongated to allow for ou...

Page 12: ...ve all swarf and system debris This can be achieved by connecting a hose to the pipework and turning on the mains water supply long enough to clear the debris to waste Procedure Turn off water supply...

Page 13: ...rews Loose connections can result in cable overheating Note The supply cable earth conductor must be sleeved The outer sheath of the supply cable must be stripped back to the minimum The supply cable...

Page 14: ...s into the upper position and the remaining neon fits into the lower position Attached to the START STOP switch inside the cover is a two wire lead Connect the socket on the end of the lead to the plu...

Page 15: ...power indicator will light Press the Start Stop button fig 20 and wait until water starts to flow from the flexible hose Slowly turn the temperature control fully anti clockwise to number 1 the maxim...

Page 16: ...t due to low water pressure it will be necessary to operate the unit on this setting during the warmer months because of flow rate limitations entering the unit The red symbol T00402 is a high power s...

Page 17: ...be a time delay of a few seconds between selecting a flow rate and the water reaching the stable temperature for that flow rate CAUTION It is recommended that persons who may have difficulty understan...

Page 18: ...as cooled sufficiently power to the elements will be automatically restored to the settings at the time of interruption Safety cut out The unit is fitted with a non resettable thermal cut out safety d...

Page 19: ...or service engineer IMPORTANT Before servicing switch off both the electricity supply and water supply at the mains The inlet filter is situated in the side of the inlet pipe fig To gain access to th...

Page 20: ...ely Power selector S12121011 Thermal cut out 22011180 Stabiliser valve Solenoid assembly P12120806 Pressure relief device PRD 82800450 Heater can assembly 8 5kW P12120701 Start Stop switch assembly 82...

Page 21: ...educe flow rate via temperature control Is water supply mains or tank fed If tank fed replumb to mains water supply or see 4 2 4 If mains fed make sure that the mains stopvalve is fully open and there...

Page 22: ...4 2 4 4 3 1 4 3 2 4 4 1 5 1 1 6 1 1 6 2 1 6 3 1 6 4 1 7 1 1 7 2 1 7 3 1 required see rating label Reduction in ambient water temperature Electrical malfunction or safety cut out operated Water pressur...

Page 23: ...y registered with the Environment Agency under the following schemes Repic Producers take back scheme PTS registration number WEE EJ3466QV Valpak Distributor take back scheme DTS registration number 9...

Page 24: ...ers Card Payment can also be made by pre payment of a pro forma invoice by cheque or postal order Telephone orders are based on information given during the call Before contacting Triton please verify...

Reviews: