Table B

Note: 

Cable selection is dependent on 

derating factors

Twin and earth PVC insulated cable

Current carrying capacity

In conduit

trunking

6mm²

38A

10mm²

52A

16mm²

69A

Installed in an 

insulated wall

6mm²

32A

10mm²

43A

16mm²

57A

Clipped direct

or buried in a 
non-insulated 

wall

6mm²

46A

10mm²

63A

16mm²

85A

6mm2

10mm2

16mm2

*The method below may be used by

installers to determine the approximate 

size of the incoming cable.

1.

Measure the width of an individual strand,
and half that measurment to find 

(r)

,

e.g: 

1.34mm ÷ 2 = (r) 0.67mm

2.

Multiply 

(r) x (r)

 x 

3.14,

e.g: 

(r)

 

0.67 x (r)

 

0.67 

3.14 = 1.41mm2

3.

Multiply this by the number of wire strands
(usually 7), e.g: 

1.41mm2 x 7 = 9.87mm2.

4.

The number obtained would suggest

10mm2

 wiring.

*PLEASE NOTE:

 If unsure, consult a qualified Electrician.

6

 

A 45 amp double pole isolating switch with 
a minimum contact gap of 3 mm in both 
poles must be incorporated in the circuit.

6.1

  It must have a mechanical indicator showing 

when the switch is in the OFF position, and 
the wiring must be connected to the switch 
without the use of a plug or socket outlet.

6.2

 The switch must be accessible and clearly 

able, but out of reach of a person 

u

xed bath or shower, except for the 

cord of a cord operated switch, and should 
be placed so that it is not possible to touch 
the switch body while standing in a bath or 
shower cubicle. It should be readily accessible 
to switch off after using the shower.

7

 

Where shower cubicles are located in any 
rooms other than bathrooms, all socket 
outlets in those rooms must be protected by 
a 30mA RCD.

8

 

The current carrying capacity of the cable 
must be at least that of the shower circuit 
protection 

(see Table B)

.

8.1

  To obtain full advantage of the power 

provided by the shower, use the shortest 
cable route possible from the consumer unit 
to the shower.

8.2

  It is also necessary to satisfy the disconnection 

time and thermal constraints which means 
that for any given combination of current 
demand, voltage drop and cable size, there is 
a maximum permissible circuit length.

9

 

The shower circuit should be separated from 
other circuits by at least twice the diameter 
of the cable or conduit.

9.1

  The current rating will be reduced if the 

cabling is bunched with others, surrounded 
by thermal loft or wall insulation or placed 
in areas where the ambient temperature 
is above 30°C. Under these conditions, 
derating factors apply and it is necessary to 
select a larger cable size.

9.2

  In the majority of installations 

(see 

Table B)

, the cable will unavoidably be 

placed in one or more of the above 
conditions. This being so, it is strongly 
recommended to use a minimum of 10mm 
cabling throughout the shower installation.

9.3

  In any event, it is essential that individual 

site conditions are assessed by a competent 
electrician in order to determine the correct 
cable size and permissible circuit length.

Summary of Contents for Excite Eco

Page 1: ...s Excite Eco electric shower 2180695E April 2018 Installers please note these instructions are to be left with the user ECO STATEMENT This product has been designed to deliver an average flow of below...

Page 2: ...ts diagram 21 Guarantee service policy etc rear cover CONTENTS Page To check the product suitability for commercial and multiple installations please contact Triton s specification advisory service be...

Page 3: ...nd could also cause the PRD Pressure Relief Device in the unit to operate 1 9 This product is not suitable for mounting into steam rooms or steam cubicles 2 PLUMBING 2 1 The plumbing installation must...

Page 4: ...ter becomes too hot and you cannot obtain cooler water first check that the sprayplate in the showerhead has not become blocked DO NOT place items such as soap or shampoo bottles on top of the unit Li...

Page 5: ...ry area 6 Wall screw fixing 7 Terminal block 8 Power selector 9 Stabilising valve 10 Solenoid valve 11 Guide pockets 12 Can and element assembly 13 Thermal cut out main 14 Earth connection 15 Pressure...

Page 6: ...bt switch off the whole installation at the mains supply and remove the correct fuse 3 The shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a ring main sp...

Page 7: ...ng in a bath or shower cubicle It should be readily accessible to switch off after using the shower 7 Where shower cubicles are located in any rooms other than bathrooms all socket outlets in those ro...

Page 8: ...tic pressure must be no greater than 1000kPa 10 bar If in any doubt the pressure should be checked Note If the stated flow rates are not available it may not be possible to achieve optimum performance...

Page 9: ...wall always mount the unit on the surface of the tiles NEVER tile up to the unit Refer to fig 6 for the correct siting of the shower Position the unit where it will NOT be in direct contact with water...

Page 10: ...ce cable entry from the top is required then a small area will need to be cut out in the backplate fig 9 If installing a feed pipe from the rear bottom or side the centre of the inlet valve to the wal...

Page 11: ...the wall Hook the backplate over the top and bottom screws and fit the centre fixing screw into position Do not fully tighten the screws at this stage as the fixing holes are elongated to allow for ou...

Page 12: ...ve all swarf and system debris This can be achieved by connecting a hose to the pipework and turning on the mains water supply long enough to clear the debris to waste Procedure Turn off water supply...

Page 13: ...rews Loose connections can result in cable overheating Note The supply cable earth conductor must be sleeved The outer sheath of the supply cable must be stripped back to the minimum The supply cable...

Page 14: ...s into the upper position and the remaining neon fits into the lower position Attached to the START STOP switch inside the cover is a two wire lead Connect the socket on the end of the lead to the plu...

Page 15: ...power indicator will light Press the Start Stop button fig 20 and wait until water starts to flow from the flexible hose Slowly turn the temperature control fully anti clockwise to number 1 the maxim...

Page 16: ...t due to low water pressure it will be necessary to operate the unit on this setting during the warmer months because of flow rate limitations entering the unit The red symbol T00402 is a high power s...

Page 17: ...be a time delay of a few seconds between selecting a flow rate and the water reaching the stable temperature for that flow rate CAUTION It is recommended that persons who may have difficulty understan...

Page 18: ...as cooled sufficiently power to the elements will be automatically restored to the settings at the time of interruption Safety cut out The unit is fitted with a non resettable thermal cut out safety d...

Page 19: ...or service engineer IMPORTANT Before servicing switch off both the electricity supply and water supply at the mains The inlet filter is situated in the side of the inlet pipe fig To gain access to th...

Page 20: ...ely Power selector S12121011 Thermal cut out 22011180 Stabiliser valve Solenoid assembly P12120806 Pressure relief device PRD 82800450 Heater can assembly 8 5kW P12120701 Start Stop switch assembly 82...

Page 21: ...educe flow rate via temperature control Is water supply mains or tank fed If tank fed replumb to mains water supply or see 4 2 4 If mains fed make sure that the mains stopvalve is fully open and there...

Page 22: ...4 2 4 4 3 1 4 3 2 4 4 1 5 1 1 6 1 1 6 2 1 6 3 1 6 4 1 7 1 1 7 2 1 7 3 1 required see rating label Reduction in ambient water temperature Electrical malfunction or safety cut out operated Water pressur...

Page 23: ...y registered with the Environment Agency under the following schemes Repic Producers take back scheme PTS registration number WEE EJ3466QV Valpak Distributor take back scheme DTS registration number 9...

Page 24: ...ers Card Payment can also be made by pre payment of a pro forma invoice by cheque or postal order Telephone orders are based on information given during the call Before contacting Triton please verify...

Reviews: