background image

DC7000 ANTIQUE  

2

INTRODUCTION

This book contains all the necessary fitting and
operating instructions for your Triton dual control
mixer shower. Please read them carefully. Read
through the whole of this book before beginning
your installation.

The shower installation must be carried out by a
suitably competent person and in sequence of this
instruction book.

Care taken during the installation will ensure a
long and trouble free life from the shower.

This thermostatic shower valve has been
independently tested and approved to all the
requirements of 

NHS Estates Model Engineering

Specification D08 Thermostatic Mixing Valves
(Healthcare Premises)

to the following

designations and for the following applications:

HP-S

Shower with supply pressures of
1 - 5 Bar and unrestricted flow rate.

LP -S

Shower with supply pressures of
0.2 - 1 Bar and unrestricted flow rate.

For optimum performance within the specified
running pressure range a minimum flow of 8 litres
per minute should be available  to both inlets.

The valve is suitable for fully modulating
type combination boilers and multi-point hot
water heaters. Also suitable for thermal
storage, unvented systems and pumped
gravity systems.

Important: Before installing with a  gas
instantaneous water heater, ensure the
appliance is capable of hot water delivery at
a minimum switch on flowrate of 3 litres per
minute. At flow rates between 3 and 8 litres
per minute the appliance must be capable of
raising the water temperature by 45°C.
Water temperature at the inlet to the mixer
must remain relatively constant when
flowrate adjustments are made.

The valve unit can be fitted in any orientation. For
a wall mounted sprayhead installation, the
plumbing will be simplified if the outlet is fitted
upwards.

The valve is supplied with an integral single check
valve and integral large area filter on each inlet.

Inlet connections are by compression fittings for

15mm copper pipe.

This valve unit is supplied with a mounting bracket
to suit installation in a chased out cavity in a solid
wall, a stud partition wall, dry lined wall or fixing
to a shower cubicle or panel. It is also supplied
with an attached tiling shroud which provides
protection for the unit.

SAFETY WARNINGS

1

Layout and sizing of pipework must be such
that when other services are used, pressures
at the shower control inlets 

do not

fall below

the recommended minimum.

2

DO NOT choose a position where the shower
could become frozen.

3

The outlet of this appliance must not be
connected to any form of tap or fitting not
recommended by the manufacturer.

4

The sprayhead must be cleaned regularly to
remove scale and debris.

5

Conveniently situated isolating valves in each
inlet supply must be fitted as an independent
method of isolating the shower should
maintenance or servicing be necessary.

6

If it is intended to operate the shower in areas
of hard water it is advisable to fit a scale
inhibitor.

7

If it is intended to operate the shower outside
the guidelines laid out in the requirements
then see NOTE below.

NOTE: In the event of items 2 and 7, contact
Triton Customer Service for advice.
Tel: (024) 7637 2222.

Replacement parts can be ordered from Triton
Customer Service. See 

‘spare parts’ 

for details and

part numbers.

Due to continuous improvement and updating,
specification may be altered without prior notice.

Summary of Contents for DC7000 Antique

Page 1: ...O L D O N O F F T R ITON SHOW E R S Installation and Operating Instructions INSTALLERS PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER 2180290B May 2000 DC7000 dual control Antique mixer...

Page 2: ...DC7000 ANTIQUE UKAS QUALITY MANAGEMENT 003...

Page 3: ...wer 6 Installation general 7 8 Installation solid wall 9 hollow wall 10 cubicle or panel 11 Connecting the supply pipes 12 Fitting Showerhead 13 Using the tiling shroud 14 Fitting the face plate and k...

Page 4: ...en flowrate adjustments are made The valve unit can be fitted in any orientation For a wall mounted sprayhead installation the plumbing will be simplified if the outlet is fitted upwards The valve is...

Page 5: ...knob 4 On off control knob 5 Tiling shroud 6 Mounting bracket 7 Flat bracket 2 off 8 Sprayhead and arm 9 Tool and screw pack 10 Ceramic on off cap 11 Ceramic temperature cap 12 Trim rings 13 Flow lim...

Page 6: ...ply pipework can provide nominally equal pressures at the mixer valve For optimum performance of this shower both hot and cold water supplies to the shower valve should be fed at nominally equal press...

Page 7: ...us water heater the appliance must be capable of raising the temperature of the incoming water by 45 C 81 F and delivering a flow rate of not less than 8 litres per minute A flow limiter is supplied f...

Page 8: ...time when it is being installed The hot and cold water pipes should not be permanently attached to the wall closer than 2m from the valve prior to installation to allow for final adjustment of the va...

Page 9: ...tted in any orientation fig 7 but for a wall mounted sprayhead installation the plumbing will be simplified if the outlet is fitted upwards Access to the integral strainers will also be improved with...

Page 10: ...65 mm fig 9 measured from the face of the wall upon which the mounting bracket is screwed excluding the tile thickness The allowance for varying thickness of tiles up to 10mm is accommodated by a limi...

Page 11: ...when the installation is complete There is limited tolerance between the control knobs and trim rings to allow for varying thickness of tiles up to 10mm As a guide for the size of hole place the tilin...

Page 12: ...ying thickness of tiles up to 10mm Mark the route of the incoming and outgoing pipework As a guide for the size of hole place the tile shroud on the wall and trace around it fig 11 Take out the plaste...

Page 13: ...of the panel or cubicle Use the supplied template as a guide fig 16 After cutting the two holes fit the valve to the mounting bracket and secure using the four screws provided Offer the valve and mou...

Page 14: ...other sealing means is required Tighten the compression fittings with the cranked spanner supplied for when access is restricted Ensure the on off assembly is turned to the off position by temporarily...

Page 15: ...oles fig 21 Drill and plug the holes using the plugs supplied NOTE If fitting to a hollow wall structure use suitable cavity wall fixtures Apply PTFE tape to the 1 2 BSP thread on the shower head arm...

Page 16: ...nsuring the indicator notch is in the 12 o clock position It must be in this position regardless in which orientation the unit is mounted Secure by screwing on the two brass face plate retaining rings...

Page 17: ...e that should the knobs and faceplate require cleaning then care must be taken not to scratch them in the process Wash away any surface dust before cleaning with soapy water DO NOT USE ABRASIVE CLEANE...

Page 18: ...an uncontrolled manner then the hot and cold supplies are probably reversed This must be corrected before proceeding further The mixer valve is factory set to provide a maximum outlet temperature of...

Page 19: ...omer Service In domestic installations where D08 specification is not required the maximum temperature setting should not exceed 45 C OPERATING THE SHOWER To start the shower rotate the on off control...

Page 20: ...ssioned setting then ensure the strainers are clean and that the isolating valves are fully open Test the non return valves as described below If these tests do not highlight the reason for the temper...

Page 21: ...f the hot supply and ensure the cold supply is open Be prepared for leakage of trapped water in the pipe and remove the strainer basket on the hot side Evidence of continuing leakage from the strainer...

Page 22: ...Spray arm chrome 22009380 gold 22009390 7 Sprayhead chrome 22009340 gold 22009330 8 Mounting bracket 7012435 9 Flat bracket 7012436 Bracket assembly 83306290 comprising 8 9 10 Utilities pack 7102523 c...

Page 23: ...sioning details Hot water temp C Pressure Bar Equip used Cold water temp C Pressure Bar Equip used Max temp setting C C W fail C max Replacement dates O ring seals recommended every 3 years Thermostat...

Page 24: ...specification 1 4 1 Clean refer to maintenance section 1 5 1 Replace refer to maintenance section 2 1 1 Turn temperature control anti clockwise 2 2 1 Turn temperature control anti clockwise 2 3 1 Ens...

Page 25: ...23 DC7000 ANTIQUE...

Page 26: ...DC7000 ANTIQUE 24...

Page 27: ......

Page 28: ...rma invoice by cheque or money order 2 By telephone quoting credit card MasterCard or Visa details 3 By website order www tritonshowers co uk Triton Plc Shepperton Park Caldwell Road Nuneaton Warwicks...

Reviews: