UPS Unit State when asserting EPO with AC line present:
LEDs
Output
Fans
Serial
SNMP
USB
OFF
OFF
ON
ON
ON
ON
To restart the UPS unit after asserting EPO with AC line present:
Option 1:
1. Verify that the EPO assertion has been removed or cleared.
2. Press OFF button until you hear a click (approx. 1 second).
3. Press ON button and UPS output will turn back on.
Option 2:
1. Verify that the EPO assertion has been removed or cleared.
2. Remove AC line power to the UPS unit.
3. Reapply AC line power. Now the UPS will start back up in normal operation mode.
UPS Unit State when asserting EPO without AC line power:
LEDs
Output
Fans
Serial
SNMP
USB
OFF
OFF
OFF
OFF
OFF
OFF
To restart the UPS unit after asserting EPO without AC line power:
1. Verify that the EPO assertion has been removed or cleared.
2. Reapply AC line power to the UPS unit. Now the UPS will start back up in normal
operation mode.
External Battery Connection
Check to ensure that the external batteries you are
connecting match the voltage listed on your UPS's
battery connector. All UPS models come with a
robust internal battery system; select models feature
connectors that accept optional external battery
packs (sold separately from Tripp Lite) to provide
additional runtime. Adding external batteries will
increase recharge time as well as runtime. See the
battery pack owner's manual for complete
installation instructions. Make sure cables are fully
inserted into their connectors. Small sparks may
result during battery connection; this is normal. Do
not connect or disconnect battery packs when the
UPS is running on battery power.
201203257 93-2486.indd 7
4/3/2012 3:12:58 PM
Summary of Contents for SmartOnline AGPS5546
Page 48: ...48 201203257 93 2486 indd 48 4 3 2012 3 13 09 PM...
Page 54: ...54 201203257 93 2486 indd 54 4 3 2012 3 13 11 PM...
Page 55: ...55 BYPASS Bypass Tripp Lite 10 BYPASS PowerAlert 201203257 93 2486 indd 55 4 3 2012 3 13 11 PM...
Page 56: ...56 201203257 93 2486 indd 56 4 3 2012 3 13 11 PM...
Page 57: ...IEC320 C13 IEC320 C19 IEC320 C20 IEC320 C14 57 201203257 93 2486 indd 57 4 3 2012 3 13 11 PM...
Page 58: ...58 201203257 93 2486 indd 58 4 3 2012 3 13 12 PM...