12
The UPS’s control panel lights will turn on in the sequences below to signal that the UPS is
having operational difficulties.
Lights (On/Flashing) and Condition
Solution
On: REPLACE BATT
Let the UPS system charge for at least
Condition: Replace Battery
12 hours and perform a self test using
the "ON/Test Switch" as described on
page 7. If the light continues to stay on,
contact Tripp Lite for service.
On: BATT LOW, ON BATT
Prepare for imminent UPS shutdown.
Condition: Battery Low
On: BYPASS, LINE, LOAD, OVERLOAD
Reduce the load the UPS supports.
Condition: On Bypass due to Overload
Flashing: OVERLOAD
Remove the cause of the short circuit
Condition: Short Circuit
from the UPS output.
On: FAULT, 100%
Restart the UPS. If the problem persists,
Condition: Battery Voltage too High
contact Tripp Lite for repairs.
On: FAULT, BYPASS, LINE, 50%
Restart the UPS. If the problem persists,
Condition: On Bypass due to
contact Tripp Lite for repairs.
High Output Voltage
On: FAULT, BYPASS, LINE
Restart the UPS. If the problem persists,
Flashing: 50%
contact Tripp Lite for repairs.
Condition: On Bypass due to
Low Output Voltage
On: FAULT, BYPASS, LINE, 25%
Restart the UPS. If the problem persists,
Condition: On Bypass due to High
contact Tripp Lite for repairs.
Bus Voltage
On: FAULT, BYPASS, LINE
Restart the UPS. If the problem persists,
Flashing: 25%
contact Tripp Lite for repairs.
Condition: On Bypass due to Low
Bus Voltage
On: BYPASS, LINE
Check the UPS to be sure that there is
Flashing: FAULT
adequate space for air to circulate near
Condition: On Bypass due to High
the vents and that the fan is working
Internal Temperature
properly. Restart the UPS.
Troubleshooting
201203257 93-2486.indd 12
4/3/2012 3:13:01 PM
Summary of Contents for SmartOnline AGPS5546
Page 48: ...48 201203257 93 2486 indd 48 4 3 2012 3 13 09 PM...
Page 54: ...54 201203257 93 2486 indd 54 4 3 2012 3 13 11 PM...
Page 55: ...55 BYPASS Bypass Tripp Lite 10 BYPASS PowerAlert 201203257 93 2486 indd 55 4 3 2012 3 13 11 PM...
Page 56: ...56 201203257 93 2486 indd 56 4 3 2012 3 13 11 PM...
Page 57: ...IEC320 C13 IEC320 C19 IEC320 C20 IEC320 C14 57 201203257 93 2486 indd 57 4 3 2012 3 13 11 PM...
Page 58: ...58 201203257 93 2486 indd 58 4 3 2012 3 13 12 PM...