8
3. Battery Cabinet Installation
3.4 Package Contents
Part Number
Description
BP240V09
BP240V09K
BP240V09-
NIB
BP240V40
BP240V40L
BP240V40-
NIB
BP240V40L-
NIB
Owner's Manual
933BF6
Yes
Yes
Yes
Yes
Yes
Yes
Battery Cable
73184C
Length 1.3 m Cables
with Anderson
connector terminals
2
2
n/a
n/a
n/a
n/a
Battery Cable
731891
Length 3 m Cables
with Anderson
connector terminals
n/a
n/a
2
2
2
2
Battery Shorts/
Jumper Cables
731856
Copper bars for
interconnecting
adjacent batteries
n/a
72
n/a
n/a
n/a
n/a
Cushion
820606
Battery cabinet
bracket/panel
assembly
n/a
16
n/a
n/a
n/a
n/a
Battery Cables
for "-NIB"
Models
Various P/N
For connecting the
battery strings to the
cabinet
n/a
n/a
n/a
n/a
9
16
Copper Jumper
Bars
1038F2
Copper bars for
interconnecting
adjacent batteries
n/a
n/a
n/a
n/a
14
28
3.5 Internal Wiring (Typical)
• Battery cabinets use multiple 12V DC batteries connected in series to provide nominal DC voltage of 240V DC (±120V DC).
• Internal cabling is sized for specific application load currents. Do not use any other cable size other than the one provided in
the battery cabinet.
• Each battery cabinet shelf includes a specific wiring diagram. Refer to section
5. Installation
for battery installation details.
• All circuit breakers are in the middle tier of the battery cabinet.
• All load connection polarities will be labeled as “+” (battery positive), “-“ (battery negative) and “N” (battery center tap) for
±120V DC strings.
• All battery cabinets are provided with a branch circuit overcurrent protection device and may be wired directly to the load or
UPS.
Summary of Contents for BP240V09
Page 38: ...38 5 Installation Figure 5 32 Wiring Diagram for Installation of 80 Batteries ...
Page 46: ...46 5 Installation Figure 5 41C Front Layer 3 Layer 2 Layer 1 Rear ...
Page 49: ...49 5 Installation Figure 5 44A 2 Remove top right side and left side plates Figure 5 44 ...
Page 54: ...54 5 Installation 14 Reinstall the covers and the screws Figure 5 53 Figure 5 53 ...
Page 113: ...113 5 Instalación Figura 5 32 Diagrama de Cableado para la Instalación de 80 Baterías ...
Page 121: ...121 5 Instalación Figura 5 41C Front Layer 3 Layer 2 Layer 1 Rear ...
Page 129: ...129 5 Instalación 14 Reinstale las cubiertas y los tornillos Figura 5 53 Figura 5 53 ...
Page 196: ...196 5 Installation Figure 5 41C Front Layer 3 Layer 2 Layer 1 Rear ...
Page 204: ...204 5 Installation 14 Réinstaller les couvercles et les vis Figure 5 53 Figure 5 53 ...