Prestige Parameter Information
17
Accessing Boiler Information
Information mode
To switch from STANDBY mode to INFORMA-
TION mode, press MODE twice.
Press STEP until the system displays the informa-
tion you need. The first digit is the information item
number followed by the items value. The decimal
point located behind the first position flashes to
indicate that the boiler is in INFO mode.
The ignition counters and burner hours are
split into three two digit numbers. For example:
Write the numbers down from left to right to
arrive at 123,456 CH ignitions.
In the INFO Mode a temperature reading of
-22 typically indicates an “open” circuit. A
temperature reading of 240 typically indi-
cates a short-circuit.