Program Access of the MCBA Control
PROGRAM ACCESS OF THE MCBA
CONTROL
The factory default setting for the PRESTIGE Control
Module to operate the IDWH is through an aquastat
control. The PRESTIGE Control Module must be pro-
grammed as described in the following instruction to
correctly operate the IDWH through the IDWH sensor.
To adjust the factory parameter settings of the PRES-
TIGE MCBA Control, the installer must enter into the
parameter menu of the control.
Do not attempt to revise any other control parameter
settings except those listed in this supplement.
Perform only those parameter revisions described in
this supplement. Failure to comply could result in
erratic or unreliable operation of the PRESTIGE
resulting in severe personal injury, death or sub-
stantial property damage.
For additional information on revising the PRES-
TIGE MCBA Control Module operational parameter
settings,
reference
the
PRESTIGE
Control
Supplement.
ACTIVATING THE ACCESS CODE
To enter the parameter listing of the MCBA control, the
installer must enter the activation code as follows:
1. Press and hold the MODE button
2. Continue holding the MODE and press STEP button
until
STBY
appears and hold both STEP and MODE
buttons for 2 to 3 seconds.
The display should read
CODE
3. Release the STEP and MODE buttons on the control
panel.
4. Press STEP once.
NOTICE
WARNING
NOTICE
The display should read
C_
XX
(XX should be
a random number from 00 to 99)
5. Press the + or - button to change the display num-
ber
C_
XX
to read
C_54
. Press and release the +
or - to change the display one number at a time.
Press and hold the + or - to rapidly change the dis-
play number.
6. When the display reads
C_54
press STORE to
save the activation code. The display
C_54
should
flash when the code is entered and saved.
After the activation code is entered press the MODE but-
ton until the display shows
PARA
. At this point the
installer can access the parameters required for applica-
tion.
Once in the parameter mode, press the STEP repeated-
ly to reach the appropriate parameter setting. The dis-
play should show the following sequence, as the STEP
button is press repeatedly:
Press STEP once-
1140
Press STEP x2 -
2_01
Press STEP x3 -
3_01
Press STEP x4 -
4186
Press STEP x5 -
P_10
Press STEP x6 -
P_11
Etc......
After Parameter 4 the display will continue to show P fol-
lowed by a two-digit number that increases with each
press of the STEP button.
The actual parameter values displayed on the
unit may vary depending on the application. The
parameter sequence will always occur in the
order shown.