TRC ELECTRONICS, INC.
Providing exceptional customer service since 1982
TRC ELECTRONICS, INC.
1.888.612.9514
www.
trcelectronics
.com
Designers Manual
Advanced Energy CoolX600 Series
TTaabbllee 55‑‑66.. Applicable PMBus commands for bulk modules (Continued)
C
Coom
mm
maanndd
D
Deessccrriippttiioonn
• Resolution: 1°C (1.8°F)
STATUS_WORD
(0x79)
Checks for the presence of fault conditions such as
OVERTEMPERATURE PROTECTION
(OTP)
signal and
POWER GOOD
(PG) fail.
PAGE
(0x00)
Selects which module the subsequent commands
will affect. When read, this command returns the
currently selected (paged) module number.
OPERATION
(0x01)
Enables or disables the output of the selected
(paged) module. When read, this command returns
the last
OPERATION
command sent to the
selected module.
VOUT_MODE
(0x20)
Returns the 5-bit exponent used to interpret
extended linear format readings for the selected
(paged) module.
VOUT_COMMAND
(0x21)
Sets the output voltage of the selected (paged)
module to the commanded value. When read, this
command returns the last
VOUT_COMMAND
value sent to the selected module.
ILIMIT_TRIM
(0xD1)
Sets the current limit of the selected (paged)
module to the commanded value. When read, this
command returns the last
ILIMIT_TRIM
value
sent to the selected (paged) module.
MODULE_ID
(0xD0)
Returns a code
representing the model
type of the selected
(paged) module.
Module
ID Code
CmE
0xBC
CmF
0xBD
TTaabbllee 55‑‑77.. Applicable PMBus commands for dual modules
C
Coom
mm
maanndd
D
Deessccrriippttiioonn
PAGE
(0x00)
Selects which module the subsequent commands
will affect. When read, this command returns the
currently selected (paged) module number.
OPERATION
(0x01)
Enables or disables the output of the selected
(paged) module. When read, this command returns
the last
OPERATION
command sent to the
selected module.
MODULE_ID
(0xD0)
Returns a code representing the model type of the
selected (paged) module. Please note this
Advanced Energy
®
CoolX
®
600 Modular Power Supply
57010208-00B
Communication Controls
5‑10