Finalizing the Installation
21
© Travis Industries
9/22/2020 - 1521
430 EG GSR2
Horizontal Termination
DuraVent manufactures a vent kit for horizontal that allows for terminating horizontally when installed in a
masonry fireplace (not for use with ZC fireplaces). The DuraVent kit (46DVA-HCL33 and 46DVA HCL34)
is approved for use with Travis Industries gas inserts.
These kits can be purchased from your Travis Industries dealer.
Application
DuraVent Part #
For inserts that use 3” exhaust and 3” intake
46DVA-HCL33
For inserts that use 3” exhaust and 4” intake
46DVA-HCL34
Refer to the kit manufacturer’s instructions for details and requirements for installation. In addition to the
manufacturer’s requirements, the following requirements must be met:
The termination center
MUST
be
a minimum of 5’ from the base of
insert.
The termination center
MUST
NOT
be more than 8’ from the
base of the insert.
The radius of any bends in the
flexible venting
MUST NOT
be
less than a 4” radius
All portions of the venting
MUST
have at least a 1/4” rise per 12” of
horizontal run
Min. 5’
Max. 8’
Radius
4” Min
r 4”